MA-037 - CB Watch 3 Operating Manual
v7.0 - May 2020
Page 115 of 118
TECHNICAL SPECIFICATION
Measurements
Continuous measurements
Feature
Value
Refresh frequency
Approx. every 1 second
Gas
measurements
Pressure accuracy
±20mBar over most of range
Temperature accuracy
±2
o
C
Gas
measurement
with moisture
Pressure accuracy
±32mBar below 0
o
C, ±10mBar
above 0
o
C
Temperature accuracy
±1
o
C
Analogue
measurements
Accuracy
0.1% of measuring range
A/D conversion
16 bit
Temperature
Accuracy
+/- 0.1
o
C (PT100 3-wire)
Time
Accuracy
1 second
Data storage
Short Term gas data
last 3,000 values @ 1 per minute
Long Term gas data
last 500 values @ 1 per day
Operations measurement
Feature
Value
Time horizon
Operation
0.3 seconds
Motor current
12 seconds
Refresh frequency
every 400 micro seconds (0.4ms)
Analogue
measurements
Accuracy
0.1% of measuring range
A/D conversion
16 bit
Time
Accuracy
+/- 1 milli second
Temperature
Accuracy
+/- 0.1
o
C (PT100 3-wire)
Data storage
Operation data
last 50 operations
Pump data
Last 5 pump starts per pump