3300/25 Dual Accelerometer Input Monitor Operation Manual
132
7.
Repeat the test for channel B.
8.
Disconnect the test equipment and reconnect the transducer input wiring to
channels A and B.
9.
Turn Danger Bypass off if you turned it on at the beginning of this procedure.
B.
The bargraph reading may be
slightly lower if you have a Low Pass
Filter with a corner frequency above
13.7 kHz. The reading will be lowest
when the corner frequency is at its
highest setting, 22.372 kHz. The
bargraph reading for this setting
should be 64% to 75% of full scale
range.