104
•
Appendix B - Profibus
B.4.
Actual Data Register Numbers (decimal)
Number Parameter
Name
Description
1 Logic
Status
Logic status of ASTAT-XT. 1 indicates:
d15: ASTAT-XT
Tripped.
d14: Motor
Stopped.
d13:
Motor in Soft Stop Process.
d12:
Motor in Start Process.
d11: Motor
is
Running.
d10: Dual_Adjust
On.
d9:
Motor is running with Energy Save On.
d8:
Motor is running at Slow Speed forward.
d7:
Motor is running at Slow Speed reverse.
d6: Reserved
d5..d0: Reserved
2
Motor Current
Current, % FLA
3
Line Voltage
Line voltage, Volts
4
Phase Sequence
1: Correct phase seq. 0: Wrong phase seq.
5 Hardwired
inputs
Discrete Hardwired control inputs:
d15..d8: Reserved.
d7: External
fault.
d6: Reserved.
d5: Reserved.
d4:
D.Adj / S.Spd / Rst (Programmable) Input.
d3:
E.Save / Rvrs / Rst (Programmable) Input.
d2: Start
Input.
d1: Soft
Stop
Input.
d0: Stop
Input.
6
DIP switch
d15..d8: Reserved.
d7:
Prevent Setting Lock - (right-most)
d6:
Enlarged Setting Ranges
d5: Language
Selection.
d4: Language
Selection.
d3:
Reserved - Must be set to Off.
d2:
Generator Starting - Set to Off.
d1: Reserved.
d0:
Min (OFF) / Max display pages- (left most)
10
Frequency
Main frequency, Hz
11 Thermistor
Resistance
Thermistor resistance, tenth Kohm.
17
Logic status at power
fail
Logic status at control power supply turns OFF.
18
Elapsed Run Time
Total Hours of motor runs.
19
Number of Starts
Total number of starts
20
Last start period
Duration of last start, Seconds
21
Last start peak I
Peak current during last starting process
22
Time to start
After too many starts trip, Seconds
23
Total trips
Total number of trips
24
Last Fault number
# of the fault that caused trip.
#
Fault
01: Over
Temperature
02: Short
Circuit
Current
03: Overload
04: Under
Current
05: Under
Voltage
06: Over
Voltage
07: Phase
Loss
08: Phase
Sequence
09: Shorted
SCR.
10:
Long Start Time
11:
Slow Speed Time