Mains supply 3 x 525 - 690 V
Model number
AF-600 FP
750
950
1050
1150
1350
1550
AF-650
GP
900
1000
1150
1250
1350
1550
Light duty (LD) current ratings (110 %):
Output current
Nominal [A] (525-550 V)
763
889
988
1108
1317
1479
MAX (60 sec) [A] (525-550 V)
839
978
1087
1219
1449
1627
Nominal [A] (551-690 V)
730
850
945
1060
1260
1415
MAX (60 sec) [A] (551-690 V)
803
935
1040
1166
1386
1557
Output
Nominal [kVA] (550 V)
727
847
941
1056
1255
1409
Nominal [kVA] (575 V)
727
847
941
1056
1255
1409
Nominal [kVA] (690 V)
872
1016
1129
1267
1506
1691
Typical shaft output
[kW] (550 V)
560
670
750
850
1000
1100
[HP] (575 V)
750
950
1050
1150
1350
1550
[kW] (690 V)
710
800
900
1000
1200
1400
Heavy duty (HD) torque (160 %):
Output current
Nominal [A] (525-550 V)
659
763
889
988
1108
1317
MAX (60 sec) [A] (525-550 V)
989
1145
1334
1482
1662
1976
Nominal [A] (551-690 V)
630
730
850
945
1060
1260
MAX (60 sec) [A] (551-690 V)
945
1095
1275
1418
1590
1890
Output
Nominal [kVA] (550 V)
628
727
847
941
1056
1255
Nominal [kVA] (575 V)
627
727
847
941
1056
1255
Nominal [kVA] (690 V)
753
872
1016
1129
1267
1506
Typical shaft output
[kW] (550 V)
500
560
670
750
850
1000
[HP] (575 V)
650
750
950
1050
1150
1350
[kW] (690 V)
630
710
800
900
1000
1200
600V Power loss Light
duty (LD) [W]
8933
10310
11692
12909
15358
17602
600V Power loss Heavy
duty (HD) [W]
7586
8683
10298
11329
12570
15258
690V Power loss Light
duty (LD) [W]
9212
10659
12080
13305
15865
18173
690V Power loss Heavy
duty (HD) [W]
7826
8983
10646
11681
12997
15763
Limits and Ranges
Overcurrent Warning
A rms Out
1648
1977
2336
2471
2965
3505
Overcurrent Alarm (1.5
sec delay)
A rms Out
1648
1977
2336
2471
2965
3505
Earth (Ground) Fault
Alarm
A rms Out
330
382
445
494
554
659
Short Curcuit Alarm
A rms Out
2094
2510
2980
3140
3766
4470
Heatsink Over Temper-
ature
°
C
95
105
95
95
105
95
Heatsink Under Tem-
perature Warning
°
C
0
0
0
0
0
0
Power Card Ambient
Over Temperature
°
C
68
68
68
68
68
68
Power Card Ambient
Under Temperature
°
C
-20
-20
-20
-20
-20
-20
Mains Phase Warning (5
sec delay)
DC Bus Ripple Vpeak
50
50
50
50
50
50
Mains Phase Alarm (25
sec delay)
DC Bus Ripple Vpeak
50
50
50
50
50
50
Table 1.6: Mains supply 3 x 525 - 690 V
High Power Service Manual for Unit Sizes 6x
8
1
Summary of Contents for AF-650 GP Series
Page 31: ...High Power Service Manual for Unit Sizes 6x 30 3...
Page 41: ...Illustration 3 7 Inverter section High Power Service Manual for Unit Sizes 6x 40 3...
Page 43: ...Illustration 3 8 Brake option High Power Service Manual for Unit Sizes 6x 42 3...
Page 97: ...High Power Service Manual for Unit Sizes 6x 96 7...
Page 111: ...High Power Service Manual for Unit Sizes 6x 110 8...
Page 121: ...High Power Service Manual for Unit Sizes 6x 120 9...
Page 134: ...11 Block Diagrams High Power Service Manual for Unit Sizes 6x 133 11...