2.8 Earthing Screened Cables
It is recommended that screened control cables be connected with cable clamps at both ends to the metal cabinet of the frequency converter. The table below
shows earth cabling for optimal results.
Correct earthing
Control cables and cables for serial communication must be fitted with cable clamps at
both ends to ensure the best possible electrical connection.
Incorrect earthing
Do not use twisted cable ends (pigtails) since these increase screen impedance at high
frequencies.
Earth potential protection
When the earth potential between the frequency converter and the PLC or other
interface device is different, electrical noise may occur that can disturb the entire system. This can be resolved
by fitting an equalizing cable next to the control cable. Minimum cable cross section is 8 AWG.
50/60 Hz earth loops
When using very long control cables, 50/60 Hz earth loops may occur that can disturb
the entire system. This can be resolved by connecting one end of the screen with a 100 nF capacitor and
keeping the lead short.
Serial communication control cables
Low frequency noise currents between frequency converters can be
eliminated by connecting one end of the screened cable to frequency converter terminal 61. This terminal
connects to earth through an internal RC link. It is recommended to use twisted-pair cables to reduce the
differential mode interference between conductors.
Table 2.3: Earthing Screened Cables
High Power Service Manual for Unit Sizes 6x
29
2
Summary of Contents for AF-650 GP Series
Page 31: ...High Power Service Manual for Unit Sizes 6x 30 3...
Page 41: ...Illustration 3 7 Inverter section High Power Service Manual for Unit Sizes 6x 40 3...
Page 43: ...Illustration 3 8 Brake option High Power Service Manual for Unit Sizes 6x 42 3...
Page 97: ...High Power Service Manual for Unit Sizes 6x 96 7...
Page 111: ...High Power Service Manual for Unit Sizes 6x 110 8...
Page 121: ...High Power Service Manual for Unit Sizes 6x 120 9...
Page 134: ...11 Block Diagrams High Power Service Manual for Unit Sizes 6x 133 11...