7.2.7 MDCIC Mounting Panel
1.
Remove top mounted safety cover from inverter module by removing attaching screws (8mm).
2.
Disconnect ribbon cable from control card.
3.
Before removing MDCIC ribbon cable from each inverter module, note which cable connects to each module for reassembly. Remove MDCIC ribbon
cable from each inverter module.
4.
Before removing rectifier control cable MK101 of MDCIC board, note for reinstallation that MK101 is left most 6-pin connector on MDCIC board. Remove
rectifier control cable from MDCIC board.
5.
Remove relay connector from MDCIC panel.
6.
Remove any customer interconnect wiring.
7.
Remove MDCIC panel by removing four screws (M5) attaching panel to inverter cabinet (one in each corner of panel).
1
2
3
4
5
6
7
4
130BX268.10
1
MDCIC mounting panel
5
Rectifier control cable MK101 (step 4)
2
Relay connector (not shown) (step 5)
6
MDCIC ribbon cable (step 3)
3
MDCIC board cover plate
7
Control card to MDCIC ribbon cable (step 2)
4
Attaching screw (step 7)
Reinstall in reverse order of this procedure.
High Power Service Manual for Unit Sizes 6x
104
7
Summary of Contents for AF-650 GP Series
Page 31: ...High Power Service Manual for Unit Sizes 6x 30 3...
Page 41: ...Illustration 3 7 Inverter section High Power Service Manual for Unit Sizes 6x 40 3...
Page 43: ...Illustration 3 8 Brake option High Power Service Manual for Unit Sizes 6x 42 3...
Page 97: ...High Power Service Manual for Unit Sizes 6x 96 7...
Page 111: ...High Power Service Manual for Unit Sizes 6x 110 8...
Page 121: ...High Power Service Manual for Unit Sizes 6x 120 9...
Page 134: ...11 Block Diagrams High Power Service Manual for Unit Sizes 6x 133 11...