4–350
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL
CHAPTER 4: SETPOINTS
Figure 4-154: Pushbutton “Tag” logic diagram
FASTPATH:
The pushbuttons, Tag, Block and Bypass Block are used for both breakers (contactor) and
switches when selected in the SLD. Only one component at the time can be selected in the
SLD.
FASTPATH:
Tagging, blocking, or bypassing block can be performed in Local Mode, and only when the
component (breaker (contactor) or switch) is selected in the SLD. The applied action of
tagging, blocking or bypassing block is retained for this component after it’s been
deselected. To change the status of the applied action, the component need be reselected.
FASTPATH:
The Local Mode control allows programming of separate pair of PBs for Open and Close
commands to breakers (contactor) and for Open and Close commands to switches. If
desired, one pair of pushbuttons can be programmed for Open and Close commands to
both breakers (contactor) and switches.
FLEXLOGIC OPERAND
BKR [X] Selected
SW [X] Selected
AND
S
Latch
R
Non-Volatile
Latch
Reset-
Dominant
positive
one shot
Tag
PB “TAG”
AND
FLEXLOGIC OPERAND
Tag ON
FLEXLOGIC OPERAND
Tag OFF
SETTING
TAGGING
Enabled = 1
OR
FLEXLOGIC OPERAND
SBO Enabled
894199A1.cdr
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...