CHAPTER 4: SETPOINTS
SYSTEM
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–85
Table 4-22: Contactor Status with both 52a and 52b configured
The following logic diagrams shos the detection logic for the contactor.
Figure 4-22: Contactor Connected/Disconnected (Racked-In/Racked-Out) detection for
withdrawable contactors
Figure 4-23: Contactor State Detection logic diagram
52a Contact
configured
52b Contact
configured
Contactor Status
Off
On
Contactor open
On
Off
Contactor closed
On
On
Contactor unknown state
Off
Off
Contactor unknown state
SETPOINT
CONNECTED
FlexLogic operand =1, Off = 0
FlexLogic operand status
AN
D
OR
FLEXLOGIC OPERANDS
Contactor Disconnected
FLEXLOGIC OPERANDS
Contactor Connected
894209A1.cdr
Setpoint
CONTACT INPUT 52a
Setpoint
CONTACT INPUT 52b
FlexLogic Operand
(52a state)
FlexLogic Operand
(52b status)
AN
D
AN
D
XO
R
30 ms
S
R
LED: ALARM
LATCH
OR
AN
D
OR
OR
RESET
(command)
AN
D
AN
D
OR
At least one contact programmed
(to output relays TRIP and CLOSE)
0 ms
TARGET MESSAGE
Contactor Not Config
FLEXLOGIC OPERANDS
Contactor Closed
FLEXLOGIC OPERANDS
Contactor Opened
FLEXLOGIC OPERANDS
Contactor Unkwn Stat
FlexLogic Operand
=1, Off = 0
FlexLogic Operand
=1, Off = 0
FLEXLOGIC OPERANDS
Contactor Configured
894206A1.cdr
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...