NX-8V2 Control
43
LOC
PG
DESCRIPTION
DEFAULT
PROGRAMMING DATA
111
28
Segment
3
1 =
Fast Loop Response.
2 =
Double End of Line Tamper zone.
3 =
Trouble zone (Day zone).
4 =
Cross Zone.
5 =
Dialer Delay zone.
6 =
Swinger zone.
7 =
Restore reporting.
8 =
Listen-In.
Segment
4
1 = Zone Activity Monitor.
2 = End of Line Resistor Defeat.
3 = Zone acts as Request to Exit input.
4 = Zone acts as access entry point
(
Do not enable this segment unless
configured with Access Control module
)
5 -8 = Reserved.
Segment 5 RESERVED
LOCATIONS 112 – 169
EVEN NUMBERED
Contains the event code sent for Contact ID or SIA and chosen from the list on pg 16.
4+2 Format Note:
If 4+2
format is being used, the number programmed in this location will be sent as the upper hex digit. The digit should be
from 1 to 15 when using 4+2 formats. The zone ID or user ID will be the lower hex digit of the zone that is in alarm.
ODD NUMBERED
The defaults listed below represent the five segments of each of those locations. Use the data from location 111 (table
above and pg 28)
LOC
DESCRIPTION
DEFAULT
PROGRAMMING DATA
112
ZONE TYPE 2 ALARM EVENT CODE
2
__
113
ZONE TYPE 2 CHARACTERISTIC SELECT
2-125-78-0-0
__ __ __ __ __
114
ZONE TYPE 3 ALARM EVENT CODE
7
__
115
ZONE TYPE 3 CHARACTERISTIC SELECT
5-1245-5678-0-0
__ __ __ __ __
116
ZONE TYPE 4 ALARM EVENT CODE
5
__
117
ZONE TYPE 4 CHARACTERISTIC SELECT
45-125-5678-0-0
__ __ __ __ __
118
ZONE TYPE 5 ALARM EVENT CODE
5
__
119
ZONE TYPE 5 CHARACTERISTIC SELECT
457-125-5678-0-0
__ __ __ __ __
120
ZONE TYPE 6 ALARM EVENT CODE
4
__
121
ZONE TYPE 6 CHARACTERISTIC SELECT
0-1245-5678-0-0
__ __ __ __ __
122
ZONE TYPE 7 ALARM EVENT CODE
0
__
123
ZONE TYPE 7 CHARACTERISTIC SELECT
2-0-78-0-0
__ __ __ __ __
124
ZONE TYPE 8 ALARM EVENT CODE
1
__
125
ZONE TYPE 8 CHARACTERISTIC SELECT
1-13-378-0-0
__ __ __ __ __
126
ZONE TYPE 9 ALARM EVENT CODE
7
__
127
ZONE TYPE 9 CHARACTERISTIC SELECT
6-1245-5678-0-0
__ __ __ __ __
128
ZONE TYPE 10 ALARM EVENT CODE
2
__
129
ZONE TYPE 10 CHARACTERISTIC SELECT
24-5-78-0-0
__ __ __ __ __
130
ZONE TYPE 11 ALARM EVENT CODE
3
__
131
ZONE TYPE 11 CHARACTERISTIC SELECT
3-0-0-0-0
__ __ __ __ __
132
ZONE TYPE 12 ALARM EVENT CODE
5
__
133
ZONE TYPE 12 CHARACTERISTIC SELECT
457-125-45678-0-0
__ __ __ __ __
134
ZONE TYPE 13 ALARM EVENT CODE
4
__
135
ZONE TYPE 13 CHARACTERISTIC SELECT
0-12458-5678-0-0
__ __ __ __ __
136
ZONE TYPE 14 ALARM EVENT CODE
7
__
137
ZONE TYPE 14 CHARACTERISTIC SELECT
5-12456-5678-0-0
__ __ __ __ __
138
ZONE TYPE 15 ALARM EVENT CODE
5
__
139
ZONE TYPE 15 CHARACTERISTIC SELECT
457-1256-5678-0-0
__ __ __ __ __
140
ZONE TYPE 16 ALARM EVENT CODE
4
__
141
ZONE TYPE 16 CHARACTERISTIC SELECT
0-12456-5678-0-0
__ __ __ __ __
142
ZONE TYPE 17 ALARM EVENT CODE
7
__
143
ZONE TYPE 17 CHARACTERISTIC SELECT
5-1245-25678-0-0
__ __ __ __ __
144
ZONE TYPE 18 ALARM EVENT CODE
5
__
145
ZONE TYPE 18 CHARACTERISTIC SELECT
457-125-25678-0-0
__ __ __ __ __
146
ZONE TYPE 19 ALARM EVENT CODE
4
__
147
ZONE TYPE 19 CHARACTERISTIC SELECT
0-1245-25678-0-0
__ __ __ __ __
148
ZONE TYPE 20 ALARM EVENT CODE
7
__
149
ZONE TYPE 20 CHARACTERISTIC SELECT
6-1245-25678-0-0
__ __ __ __ __
150
ZONE TYPE 21 ALARM EVENT CODE
15
__
151
ZONE TYPE 21 CHARACTERISTIC SELECT
24-15-78
__ __ __ __ __
152
ZONE TYPE 22 ALARM EVENT CODE
20
__
153
ZONE TYPE 22 CHARACTERISTIC SELECT
24-15-78
__ __ __ __ __
154
ZONE TYPE 23 ALARM EVENT CODE
21
__
155
ZONE TYPE 23 CHARACTERISTIC SELECT
24-15-78
__ __ __ __ __