92
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
FIELDBUS INTERFACE
CHAPTER 1: COMMUNICATIONS GUIDE
Table 15: DPV1 acyclic write data
Profibus DPV1-
Diagnostics
MM300 DPV1 diagnosis data is structured as shown below:
The extended diagnosis consists of Process Alarms and Diagnostic Alarms.
Trip, Alarm, and Control status are categorized as Process Alarms, as these provide
information pertaining to the Motor health that MM300 is controlling and monitoring.
Messages are categorized as Diagnostic Alarms as these provide detailed MM300
diagnostic information.
The detailed message layout explaining what information each bit provides is as follows:
Object
Slot
Index
Value
Description
Dec
Hex
0
0
0
1
0x01
Reset
0
0
0
2
0x02
Lockout Reset
0
0
0
4
0x04
Stop
0
0
0
8
0x08
Start A
0
0
0
16
0x10
Start B
0
0
0
66
0x42
Clear Last Trip Data Prompt
0
0
0
67
0x43
Reset MWh and Mvarh Meters
0
0
0
68
0x44
Clear Counters
0
0
0
69
0x45
Clear Event Records
0
0
0
70
0x46
Clear Waveform Data
0
0
0
71
0x47
Clear Maintenance Timer
0
0
0
72
0x48
Clear RTD Maximums
0
0
0
73
0x49
Reset Motor Information
0
0
0
74
0x4A
Auto Mode
0
0
0
75
0x4B
Manual Mode
0
0
0
76
0x4C
Manual Inhibit
0
0
0
77
0x4D
Manual Restore
0
0
0
78
0x4E
Start Inhibit
0
0
0
79
0x4F
Start Restore
0
0
0
80
0x50
Trigger Waveform Capture
0
0
0
81
0x51
Start Datalog
0
0
0
82
0x52
Stop Datalog