72
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
FIELDBUS INTERFACE
CHAPTER 1: COMMUNICATIONS GUIDE
Table 11: Profibus LED indications
When used for Profibus, the Fieldbus port has the following characteristics.
•
Baud rate: 9600, 19200, 31250, 45450, 93750, 187500, 500000, and 1.5M bps (auto-
detect) *
•
Address: 1 to 126
•
Vendor ID: 4D20 (hex)
•
Data table size: inputs = 174 bytes, outputs = 2 bytes
•
To be actioned, output bit must be 1 for a minimum time of 100 ms.
* Profibus communications will operate only in 1.5Mbps or auto-detect with the present
implementation. Auto-detect includes baud rates 19.2 kbps, 187.5 kbps, 500 kbps, and 1.5
Mbps.
The Profibus DP Master must read the GSE (Device Master Data) file of the MM300 for the
purposes of configuration and parameterization. The GSE file for the MM300 is named
GEMU4D20.gse.
Profibus power supply
configuration
The Profibus port has two modes of powering the electronics: internal or external. In
internal mode, a local 5 V is used, so no external voltage is required (pin 1 and pin 5 of the
connector). In external mode, the user must supply an external bus voltage on pin1 and
pin 5 of the connector. Profibus is shipped from the factory configured for internal mode.
Use the figures below to configure the the comms board power supply.
Figure 1: Comms board power supply configuration
LED
Color
Description
MS
Green
Processor OK
Off
Processor FAIL
NS
Green
Communications to master OK
Red
Communications to master FAIL
Protocol Options
SW1
SW2
SW3
SW4
DeviceNet
ON
ON
OFF
OFF
Profibus
OFF
OFF
ON
ON
PROFIBUS WITH INTERNAL SUPPLY
PROFIBUS WITH EXTERNAL SUPPLY
ON
ON
853845A1.CDR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
= switch position