CHAPTER 1: COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
59
5
ESD Trip / Stop
FC144
32 bits
LED Status
Bit 0
Running Red
Bit 1
Running Green
Bit 2
Stopped Red
Bit 3
Stopped Green
Bit 4
Tripped Red
Bit 5
Tripped Green
Bit 6
Alarm Red
Bit 7
Alarm Green
Bit 8
Auto Red
Bit 9
Auto Green
Bit 10
Manual Red
Bit 11
Manual Green
Bit 12
Comms OK Red
Bit 13
Comms OK Green
Bit 14
USER1 Red
Bit 15
USER1 Green
Bit 16
USER2 Red
Bit 17
USER2 Green
Bit 18
USER3 Red
Bit 19
USER3 Green
Bit 20
50% Red
Bit 21
50% Green
Bit 22
80% Red
Bit 23
80% Green
Bit 24
100% Red
Bit 25
100% Green
FC145
16 bits
Element Status 1
Bit 0
Level
Bit 1
Operated
Bit 2
Latched
Bit 3
Spare
FC147
16 bits
LED Intensity
0
Level 1
3
Level 2
6
Level 3
9
Level 4
12
Level 5
15
Level 6
FC148
16 bits
Trace Memory Trigger Mode
0
Retrigger
1
One-Shot
FC150
32 bits
IP Address
IP address, subnet mask or default gateway Each byte in this register represents one octet of an IP
address For example: 0x015EDA1F represents address 19421831
Code
Type
Definition