CHAPTER 1: COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU)
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
15
30413
019C
Phase B Reactive Power
-50000
50000
1
kvar
F2
0
1
30414
019D
Phase B Power Factor
-99
100
1
eUnitPF
F21
0
1
30415
019E
Phase C Real Power
-50000
50000
1
kW
F2
0
1
30416
019F
Phase C Apparent Power
0
50000
1
kVA
F13
0
2
30418
01A1
Phase C Reactive Power
-50000
50000
1
kvar
F2
0
1
30419
01A2
Phase C Power Factor
-99
100
1
eUnitPF
F21
0
1
30420
01A3
Reserved
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
30425
01A8
Reserved
1
TEMPERATURE METERING
30426
01A9
Internal Temp
-40
125
1
°C
F4
0
1
30427
01AA
Hottest Stator RTD
---
---
---
---
F1
N/A
1
30428
01AB
Hottest Stator RTD
---
---
---
°C
F4
N/A
1
30429
01AC
RTD 1 Temp
---
---
---
°C
F4
N/A
1
30430
01AD
RTD 2 Temp
---
---
---
°C
F4
N/A
1
30431
01AE
RTD 3 Temp
---
---
---
°C
F4
N/A
1
30432
01AF
RTD 4 Temp
---
---
---
°C
F4
N/A
1
30433
01B0
RTD 5 Temp
---
---
---
°C
F4
N/A
1
30434
01B1
RTD 6 Temp
---
---
---
°C
F4
N/A
1
30435
01B2
Thermistor
---
---
---
ohms
F1
N/A
1
30436
01B3
Internal Temp Max
-40
125
1
°C
F4
0
1
30437
01B4
Reserved
---
---
---
---
---
---
1
30438
01B5
Reserved
---
---
---
---
---
---
1
30439
01B6
Reserved
---
---
---
---
---
---
1
DEMAND METERING
30440
01B7
Current Demand
0
100000
1
A
F10
0
2
30442
01B9
Real Power Demand
-50000
50000
1
kW
F13
0
2
30444
01BB
Reactive Power Demand
-50000
50000
1
kvar
F13
0
2
30446
01BD
Apparent Power Demand
0
50000
1
kVA
F2
0
1
30447
01BE
Peak Current Demand
0
100000
1
A
F10
0
2
30449
01C0
Peak Real Power Demand
-50000
50000
1
kW
F13
0
2
30451
01C2
Peak Reactive Power Demand -50000
50000
1
kvar
F13
0
2
30453
01C4
Peak Apparent Power Demand 0
50000
1
kVA
F2
0
1
30454
01C5
Reserved
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
30466
01D1
Reserved
1
MOTOR STARTING LEARNED DATA
30467
01D2
Learned Acceleration Time
---
---
---
s
F2
N/A
1
30468
01D3
Learned Starting Current
---
---
---
A
F10
N/A
2
30470
01D5
Learned Starting Capacity
---
---
---
%
F1
N/A
1
30471
01D6
Reserved
---
---
---
---
---
---
1
▼
▼
▼
▼
▼
▼
▼
▼
▼
▼
30483
01E2
Reserved
---
---
---
---
---
---
1
30484
01E3
Average Motor Load Learned
---
---
---
%FLA
F3
N/A
1
RTD MAXIMIUM TEMPERATURE
30485
01E4
RTD 1 MAX Temp
---
---
---
°C
F4
N/A
1
Modbus
Hex
Description
Min
Max
Step
Units
Format Default
Size in