Note: Link between 3 and 11 to be wired on-site
The following drawing shows how to wire the detector to act as a current sink non-
isolated transmitter (3-wire connection):
F
IGURE
18
–
S
INK
3-W
IRE
S
CHEME
Note: Link between 4 and 12 to be wired on-site
4 Wire Relay Connection
This wiring option uses the fault and alarm relay and is connected to fire alarm panels.
This connection allows connecting of several detectors on 4 wires in a single loop. On
the last detector, there is a connected EOL resistor in the connection box. The value of
the resistor depends on the control panel specification.
The number of detectors in a single loop depends on the control panels power supply
capacity and length of wire width.
In a fault condition, the fault relay will open the contact. The control panel will see an
open-loop and will report a fault.
In alarm conditions, the alarm relay will close the contact and short the loop. With this
configuration, the panel does know which detector in the loop caused the alarm or fault.
See figure below.
F
IGURE
19
-
4
W
IRE
R
ELAY
C
ONNECTION
Controller
24VDC
Return
Detector
1
2
3
1
4