Harsh substances: For example, acidic liquids, gases, or solvents that may
attack the windows, metals, seals or polymeric materials.
•
Suitable precautions: For example, regular checks as part of routine
inspections or establishing from the material’s datasheet that it is resistant to
specific chemicals.
Specific conditions for use
•
The equipment is not intended to be repaired by the user. Repair of this
equipment shall be carried out by the manufacturer per the applicable code of
practice.
•
The flame paths are not intended for repair. Contact the manufacturer if the flame
paths are damaged.
•
Consult the manufacturer for a genuine replacement cover and housing to
connection box fasteners. M6x1x18 Hexagonal Socket head fasteners with a
minimum of ISO 4762 Grade A4 Class 80 are acceptable alternatives.
•
One suitably certified stopping plug is supplied with the detector.
•
The external earthing connection consists of a cable lug with an M5x10 stainless
steel screw, the terminals are suitable for connection of a wire of at least 4mm
2
/
12AWG.
•
The internal terminals are suitable for the connection of a wire equal to or greater
than the power input wiring and at a minimum of 1mm
2
/ 17AWG conductor.
Mounting the Tilt Mount
The tilt mount enables the detector to be rotated up to 45 degrees (horizontal/vertical) in
all directions. The following installation instructions show how to use it to support the
detector from below (the preferred method).
To install the tilt mount:
a)
Mount the tilt mount base (Figure 11: Tilt Mount Base - Plate View) to a solid
structure using four suitable fixings through the four 7mm (0.28
")
diameter holes.
Four captive screws with spring washers are provided in the tilt mount.
Figure 11: Tilt Mount Base - Plate View