For more information & technical support: [email protected]
10
76-M-6010-02-02
F-Guard IR3 HD User Manual
Preparations for Installation
The installation must comply with national and
local regulations and standards
applicable to
flame detectors
(e.g.,
NFPA 72) and all local and common engineering practices. It is
recommended to consult with the authority having jurisdiction.
Before installation:
•
Make sure that you have all the components and tools required to complete the
detector installation readily available before beginning installation. In cases
where you cannot complete the installation in a single session, secure and seal
the detectors and conduits before leaving the site.
•
Use colour-coded conductors or suitable wire markings or labels for the wiring.
You may use 14 to 17 AWG (2.5mm
2
to 1.0mm
2
) multi-strand wires for the site
wiring. The selection of wire gauge should be based on the number of detectors
used on the same line and the distance from the control unit, in compliance with
specifications.
•
Individually screen twisted pair cable is recommended for RS485 terminals.
•
Use suitably rating wire for the applicable certification and temperatures.
Required Tools
The detector can be installed using the following tools:
Tool
Function
Hex. KEY 6 mm
Vertical alignment
Hex. KEY 10 mm
Horizontal alignment
Wrench 13 mm
Mounting the detector
Flat Screwdriver 6 mm
Ground screw connection
Flat screwdriver 3.5mm
Terminal connection
Certification Instructions
Warnings
•
Do not open the detector, even when isolated, when a flammable atmosphere
is present.
•
The equipment may be used in hazardous areas with flammable gasses and
vapours with apparatus groups IIC, IIB and IIA and with temperature classes
T1, T2, T3, T4 and T5. See details of the explosion-proof approvals in section
•
The equipment is certified for use in ambient temperatures in the range of -
67°F to +167°F (-55°C to +75°C) or -67°F to +185°F (-55°C to +85°C) and
should not be used in temperatures outside this range.
•
Installation shall be carried out per the applicable code of practice by suitably
trained personnel.
•
Inspection and maintenance of this equipment shall be carried out by suitably
trained personnel per the applicable code of practice.
•
If the equipment is likely to come into contact with corrosive and/or other
harsh substances, consult with the relevant technical persons to take suitable
precautions to prevent the detector from being adversely affected, thus
ensuring that the type of protection is not compromised.