GASSONIC OBSERVER-i
57
0x0014
CH2 Format
Set/view channel 2 data
format
(8N1, 8E1, 801, 8N2)
Code
0, 1, 2, 3
R/W
0x0015
Software Rev
Hi
Embedded software minor
revision
ASCII
chars
Alphanumeric
R
0x0016
Reset Alarms
Set to clear all alarms
Numeric
Value
0 R/W
0x0017
Cal Sub Mode
Shows the stages of
Calibration
Numeric
Value
See description
R
0x0018
Acoustic Test
Initiates the acoustic test
routine
Numeric
Value
0 – 1
R/W
0x0019
HazardWatch
Enables HazardWatch flag
Numeric
Value
0 -1
R/W
0x001A
Relay State
Indicates the state of relays
Bit
Map
See description
R
0x001B
Alarm Latch
Set/clear alarm latching state
Numeric
Value
0 or 1
R/W
0x001C
Relay Energize
Set/clear relay energize state
Numeric
Value
0 or 1
R/W
0x001D
HART Enable
Enable HART on channel 2
Numeric
Value
0 or 1
R/W
0x001E
HART Test
Test HART communication
Numeric
Value
0, 1, 2
R/W
0x001F
Cal Abort
Abort calibration
Numeric
Value
1
R/W
0x0020
Ch1 UART
Receive Errors
Total number of UART
channel 1 receive errors
Numeric
Value
0 – 65535
R
0x0021
Ch1 Bus
Activity Rate
Serial Ch1 bus activity rate
Numeric
Value
0 – 100
R
0x0022
Ch1 Function
Code Errors
Number of Modbus channel 1
function code errors
Numeric
Value
0 – 65535
R
0x0023
Ch1 Starting
Address
Errors
Number of Modbus channel 1
starting address errors
Numeric
Value
0 – 65535
R
0x0024
Ch1 Register
Errors
Number of Modbus channel 1
register errors
Numeric
Value
0 – 65535
R
0x0025
Ch1 CRC Hi
Errors
Number of Modbus channel 1
Hi CRC errors
Numeric
Value
0 – 65535
R
0x0026
Ch1 CRC Lo
Errors
Number of Modbus channel 1
Lo CRC errors
Numeric
Value
0 – 65535
R
0x0027
Ch1 Parity
Errors
Number of serial channel 1
parity errors
Numeric
Value
0 – 65535
R
0x0028
Ch1 Overrun
Errors
Number of serial channel 1
overrun errors
Numeric
Value
0 – 65535
R
0x0029
Ch1 Framing
Errors
Number of serial channel 1
framing errors
Numeric
Value
0 – 65535
R
0x002A
Ch1 Modbus
Receive Errors
Total number of Modbus
channel 1 receive errors
Numeric
Value
0 – 65535
R
0x002B
Factory
Defaults
Set factory defaults for alarm
and relay settings
Numeric
Value
1
R/W
0x002C
Clear Ch1
UART Errors
Clears UART total receive
error counters
Numeric
Value
0
R/W
0x002D
Clear Ch1
Modbus Errors
Clears Modbus total receive
error counters
Numeric
Value
0
R/W
0x002E
HART Min AO
Sets minimum analog output
current for HART protocol
Numeric
Value
0 – 3.5 mA
1 – 1.25 mA
R/W
0x002F
HART Present
Flag
Indicates presence of HART
hardware
Numeric
Value
0 – not present
1 – present
R