GASSONIC OBSERVER-i
29
4.5.1. Setting / Checking Detection Mode and Analog Output Mode
The Detection Mode can be set by placing the magnet at the MENU button during start up for 5
seconds. At the end of the start-up, the Gassonic Observer-i will go to the detection set up menu by
displaying “ENON” for Enhanced Mode On or “ENOF” for Enhanced Mode off. “ENOF” means the
Gassonic Observer-i
is in Classic Mode.
The Classic Mode has only one analog output mode: 4-20 mA represents 40-120 dB. The Gassonic
Observer-i
automatically switches to this current mode when the Classic Mode is selected.
The Gassonic Observer-i will default to Discrete SPL (EAO1) when Enhanced Mode is selected. If the
user wants to change the Enhanced Analog output mode, after “ENON” is selected, press the MENU
button and the display will show “EAO1”. Use the UP and DOWN button to select the available current
modes.
To check the Detection Mode or Analog Output Mode, press the MENU button when the Gassonic
Observer-i is in standby, the Gassonic Observer-i
will flash the options below for 2 seconds:
•
“CLSM”: Gassonic Observer-i is in Classic Mode.
•
“EAO1”: Gassonic Observer-i is in Enhanced Mode and Analog output is in Discrete SPL
mode.
•
“EAO2”: Gassonic Observer-i is in Enhanced Mode and Analog output is in Discrete mode
.
•
“EAO3”: Gassonic Observer-i is in Enhanced Mode and Analog output is in Full SPL mode.