Universal LPG
(the appliance test point is located at the injector)
Gas pressure must be checked to confirm the appliance operating pressure is
2.75 kPa, the appliance test point is the rapid burner injector as shown below.
1. Disconnect power.
2. Light the auxiliary burner and set to high flame. Ensure all other burners are off.
3. Zero manometer, then apply flexible tubing to seal over the Rapid burner
injector, hold securely in place and check the gas pressure by pressing in the
corresponding burner control knob in, then turning to high flame position.
4. If the pressure is 2.75 kPa, reassemble the burner and perform the final checks
as per this instruction manual.
5. If the pressure is not 2.75 kPa, disconnect the appliance and check, adjust or
replace the LPG cylinder regulator(s) as appropriate in accordance with
AS/NZS 5601.
Alternative: If the appliance is supplied with an LPG test point adapter; then this
component maybe fitted to the inlet connection for the purpose of a test point
.
ADJUSTING THE BURNER MINIMUM FLAME HEIGHT:
NOTE: This adjustment can only be performed by the installer or an authorised
service personnel.
The minimum burner flame is factory adjusted for the gas type stated on the gas
type label adjacent to the gas connection and should not require adjustment.
Adjustment may be required if the hotplate has been converted from Natural gas
to Universal LPG or vice versa.
GAS CONVERSION INSTRUCTIONS:
The manufacturers servicing instructions detail how authorised personnel may
convert the hotplate from Natural gas to Universal LPG or from Universal LPG to
Natural gas. Contact the manufacturer or agent as required.
Injector
7 mm box spanner
7 mm box spanner
11