The compressed air supply must be delivered into the distribution system at a temperature not
exceeding 15
°
F above the ambient level in order to protect other devices (e.g., filters, dryers, tools,
etc) against damage. At 100 psi of discharge pressure, the air core allows the flow of 1045 cfm with
3.9 psid pressure loss (VS170 package).
AIR-COOLED HEAT EXCHANGERS
– Air-cooled cores (radiator-type) are provided as standard feature.
Two (2) radial fans, located behind the fresh air inlet grille, pump the required amount of cooling air and
expel it through an opening on the enclosure roof. Each fan is driven by a close-coupled, IP54-protected,
electric motor which also includes an integrated electronic controller for variable speed modulation and
fan overload protection.
Refer to Figure 6-1 for estimates of ventilation requirements. Please note that the air-cooled package
requires the combined total of the heat exchanger plus the enclosure ventilation flow rates (which include
motor ventilation and compressor intake). Furthermore, when package location makes it necessary to
duct fresh cooling air in/out, these ducts must be sized with a maximum (total) pressure loss of .1 inch
water gauge to avoid impacting the heat exchanger cooling air system. An external ventilation fan may
be required to properly evacuate hot air from the compressor room.
Minimum Cooling Air Flow Requirements
CFM
KW
Air-Cooled
Heat
Exchangers
Enclosure
Ventilation
Fans
135
9300
4712
170
14900
5240
Figure 6-1 – AIR FLOW CHART
All the required hardware, mechanical and electrical connections have been made at the Gardner Denver
factory, thus the only regular maintenance required is to keep the exterior core fins free from dirt and
other airborne debris per the following procedure:
Air-cooled heat exchanger cores are fabricated from aluminum. Do not use
caustic liquids to cleanse core or permanent damage will take place.
1. Be sure the unit is completely off and that oil reservoir is depressurized.
2. Disconnect, lockout and tagout power supply to the compressor package.
3.
4. Open and/or remove enclosure door panels adjacent to cooler assembly
– See Fig 1-3, Pg 10, for
details.
5.
6. Prior to do any cleaning of the heat exchanger cores, cover the main motor roof vents, air filter intake
vent (opening faces upwards), and Smart mixing valve assembly with suitable water-proof material
(e.g., plastic sheet). This will avoid depositing debris and/or water on these areas.
7. Inspect core area. If blocked with debris, use a moderate (e.g., 100psi) source of compressed air
and/or water while directing nozzle (pointed downward through core) to dislodge debris and clean.
Vacuum (applied from outside) can also be employed to clean the heat exchanger cores.
8.
9. Remove all loose debris and water from cooler box after cleaning process is complete. Also remove
temporary covers on main motor roof vents, air filter intake, and Smart valve assembly.
10. Re-install enclosure door panels.
Summary of Contents for AirSmart VS135A
Page 29: ...13 18 607 Page 28 Figure 4 2 PIPING AND INSTRUMENTATION ILLUSTRATION 305CGF797 A Ref Drawing...
Page 31: ...13 18 607 Page 30 300CGF546 D Ref Drawing Page 2 of 4...
Page 32: ...13 18 607 Page 31 300CGF546 D Ref Drawing Page 3 of 4...
Page 33: ...13 18 607 Page 32 300CGF546 D Ref Drawing Page 4 of 4...
Page 35: ...13 18 607 Page 34 302CGF546 E Ref Drawing Page 2 of 4...
Page 36: ...13 18 607 Page 35 302CGF546 E Ref Drawing Page 3 of 4...
Page 37: ...13 18 607 Page 36 302CGF546 E Ref Drawing Page 4 of 4...
Page 39: ...13 18 607 Page 38 303CGF546 C Ref Drawing Page 2 of 4...
Page 40: ...13 18 607 Page 39 303CGF546 C Ref Drawing Page 3 of 4...
Page 41: ...13 18 607 Page 40 303CGF546 C Ref Drawing Page 4 of 4...
Page 43: ...13 18 607 Page 42 305CGF546 C Ref Drawing Page 2 of 4...
Page 44: ...13 18 607 Page 43 305CGF546 C Ref Drawing Page 3 of 4...
Page 45: ...13 18 607 Page 44 305CGF546 C Ref Drawing Page 4 of 4...
Page 81: ......