LOCATION
- The compressor package shall be installed in a clean, well-lighted, well-ventilated area with
ample space all around for maintenance. Select a location that provides a cool, clean, dry source of air.
In some cases it may be necessary to install duct works to reach a source of adequate cooling air or to
direct cooling air in and out of the compressor package, to prevent recirculation (e.g., hot cooling air
entering the fresh air inlet). The package is designed to operate at ambient temperatures ranging from
40
°
F to 113
°
F (at up to 1000 meter elevation). Contact Gardner Denver for package operation at
conditions exceeding the stipulated values.
A typical ventilation arrangement is shown in Figure 2-1.
Figure 2-1 – TYPICAL COMPRESSOR ROOM
When selecting the compressor package location, be aware that its noise level may increase above its
advertised free-field condition by reflections from nearby objects (e.g., walls, machinery, etc) or by noise
from nearby machinery.
Air-Cooled Units
- Separate air and oil coolers are supplied as standard equipment on all air-cooled
packages. The heat exchangers require sufficient cooling air flow to operate efficiently
– please refer to
Section 6, Fig 6-1 of this manual for detailed instructions on the operation and maintenance of air-cooled
heat exchangers, including minimum heat exchanger cooling and enclosure ventilation requirements.
Cooling air for the heat exchangers, main motors, and electronics box is drawn in at the intake grill end of
the enclosure and is exhausted through a roof vent. Refer to Package Illustrations on Figure 1-2 and,
Figure 1-3, pages 9 and 10, for hardware details.
Do not block flow of air entering or exiting the enclosure - allow a minimum of 3-1/2 feet (1.1 m) clearance
to the nearest obstruction all around and on top.
Water-Cooled Units
– Separate brazed plate-type coolers for air and oil services are supplied on water-
cooled packages. The heat exchangers require sufficient cooling water flow to operate efficiently
– please
refer to Section 6 of this manual for detailed instructions on the operation and maintenance of water-
cooled heat exchangers, including minimum cooling water flow requirements.
Summary of Contents for AirSmart VS135A
Page 29: ...13 18 607 Page 28 Figure 4 2 PIPING AND INSTRUMENTATION ILLUSTRATION 305CGF797 A Ref Drawing...
Page 31: ...13 18 607 Page 30 300CGF546 D Ref Drawing Page 2 of 4...
Page 32: ...13 18 607 Page 31 300CGF546 D Ref Drawing Page 3 of 4...
Page 33: ...13 18 607 Page 32 300CGF546 D Ref Drawing Page 4 of 4...
Page 35: ...13 18 607 Page 34 302CGF546 E Ref Drawing Page 2 of 4...
Page 36: ...13 18 607 Page 35 302CGF546 E Ref Drawing Page 3 of 4...
Page 37: ...13 18 607 Page 36 302CGF546 E Ref Drawing Page 4 of 4...
Page 39: ...13 18 607 Page 38 303CGF546 C Ref Drawing Page 2 of 4...
Page 40: ...13 18 607 Page 39 303CGF546 C Ref Drawing Page 3 of 4...
Page 41: ...13 18 607 Page 40 303CGF546 C Ref Drawing Page 4 of 4...
Page 43: ...13 18 607 Page 42 305CGF546 C Ref Drawing Page 2 of 4...
Page 44: ...13 18 607 Page 43 305CGF546 C Ref Drawing Page 3 of 4...
Page 45: ...13 18 607 Page 44 305CGF546 C Ref Drawing Page 4 of 4...
Page 81: ......