background image

7

For low and high temperature alarm, assign alarm to
number of Temperature Indicator LEDs illuminated:
3 = low, 20 = high

(4) Day of week (1 = Sunday, 7 = Saturday)
(5) Time (24 hour format, hour, minutes)
(6) Hours to service (0-9999)
(7) Operating mode, M=X (S = schedule  running,

M = manual override)

For remote start/stop operation - while powered up,
operator is allowed to change to any of the following by
sending the ASCII code below:

Operating  State

ASCII  Code

schedule mode, compressor off

“CTRL-Q”

schedule mode, compressor on

“CTRL-R”

manual mode, compressor off

“CTRL-S”

manual mode, compressor on

“CTRL-T”

F.

Using the factory wired auxiliary contact (option)
If ordered with this option the monitor is equipped with
an auxiliary set of dry (volt-free) contacts (one set of
normally open contacts, and one set of normally closed
contacts) which can be used to operate an auxiliary
device (e.g., an air line solenoid valve). Rating 5 amps @
24VDC or 240VAC

1.

These contacts can be activated in one of the following
modes: (depending on options ordered)

a.

Schedule Driven Mode - the contacts will be
energized and de-energized according to the
schedule inputted by the operator of the dryer.  If
the refrigeration compressor shuts down on a fault
condition, the contacts will remain energized (or de-
energized) according to the schedule.  The contacts
will operate independently of the refrigeration
compressor in both the manual override and
schedule running modes.

NOTE: The mode is factory set based on the option ordered.

b.

Dryer Driven Mode- the contacts will be energized
and de-energized in parallel with the refrigeration
compressor of the dryer. Therefore, if the
refrigeration compressor is on, the contacts are
energized; if the refrigeration compressor is off
(manually or by a system fault condition), the
contacts will be de-energized.

NOTE: It is the responsibility of the end-user to properly
design the system control circuitry when using the auxiliary
contact feature.

c.

To change the factory set Schedule Driven or Dryer
Driven modes:

1.

De-energize unit and disconnect the power
supply to the dryer.

2.

Remove the cabinet panels as necessary to
provide access to the Monitor panel.

3.

On the rear of the circuit board, locate the
jumper pins labeled JA and JB.

4.

Move the jumper to the appropriate setting:
Schedule Driven: jumper position JA
Dryer Driven:  jumper position JB

5.

Wire the auxiliary device into the terminals
1 (Normally Open), 2 (Common) and/or 3
(Normally Closed) on the terminal block TB2.
See wiring diagram for details.

6.

Reinstall the cabinet panels.

7.

Energize the unit.

HIGH TEMPERATURE - compressed air
temperature is above the set point.

NOTE: If temperature probe is shorted, Temperature indicator
will be completely illuminated.

DRAIN - electric drain contains a high water level
alarm that activates if drain fails to discharge.

f.

Check drain operation - push 

Drain

 (push-to-test)

button to energize electric drain.  A flow of
condensate and/or air should be present at the
drain outlet.

E.

Using the RS-232 port
The RS-232 port is used to monitor dryer operation and
provide remote start/stop capability from a host com-
puter. A (1 to 1) DB-9 cable is required to connect dryer
and computer.  For PC connections, data is transmitted
on pin 2, received on pin 3, ground is pin 5, pins 7 and 8
are jumpered at dryer.

Operation is at fixed baud rate of 2,400; asynchronous
format is 8 bit, no parity, 1 stop bit (“8,N,1”). No  check
sum or error correction values are provided. If required,
request status string two (or more) times and compare
for agreement.

Request data by sending ASCII ? character (3FH). Re-
sponse may take up to two seconds as certain processing
functions may require completion before serial port is
acknowledged.
Dryer responds with line feed (0AH), carriage return (0DH),
and character string:
(1)    (2)   (3)    (4)     (5)       (6)     (7)
XXX,  X,  XXX,   X,   XXXX,   XXXX,  X
(1) Number of Temperature Indicator LEDs

illuminated (1-20)

(2) Compressor state, C=X (1or 031H = ON, 0 or

030H= OFF)

(3) Sum of alarm weights, A=XXX (0 - 255; e.g. high

pressure and service alarms = 132 [4 + 128])
Bit

Weight  Alarm

2

     4

 High press. alarm (1 = alarm)

3

     8

 Low press. alarm (1 = alarm)

5

    32

 Drain alarm (1 = alarm)

7

   128

 Service (service required) alarm
(1 = alarm)

Summary of Contents for 9VXRD Series

Page 1: ...00 9VXRD3000 SERVICE DEPARTMENT 724 746 1100 INSTRUCTION MANUAL CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 9 ENGINEE...

Page 2: ...ge be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found...

Page 3: ...nches 610 mm of clearance in front of dryer E Standard units are designed to operate in ambients Air cooled 45 to 110 F 7 to 43 C Water cooled 45 to 130 F 7 to 54 C F Dryer is designed to operate at a...

Page 4: ...3 4 C At installation install the petcock on the bulkhead fitting for the manual drain For manual draining convenient dryer depressurization and EDD service a three way valve at the bottom of the mois...

Page 5: ...yer disconnect switch provided by others sec NEC 24 hours before refrigeration compressor is started Never use the disconnect switch to shut down the dryer for a extended period of time except for rep...

Page 6: ...restored after power interruption 7 To reinstitute SCHEDULE RUNNING If compressor is scheduled to be off push Set Run button to restart schedule If compressor is scheduled to be on push On Off button...

Page 7: ...edule Driven or Dryer Driven modes 1 De energize unit and disconnect the power supply to the dryer 2 Remove the cabinet panels as necessary to provide access to the Monitor panel 3 On the rear of the...

Page 8: ...t that must be removed is the upper shell cap Remove the insulation from the upper shell cap Check to be sure the unit is depressurized b Remove the two bolts on the upper shell coupling 3 and the upp...

Page 9: ...t 200 psig and 100 F ambient air temperature is 80 F and a 45 F dew point temperature is desired Answer 1 000 x 1 22 x 1 12 x 1 2 1 640 scfm TABLE 2 Air capacity correction factors Multipliers MODEL 1...

Page 10: ...ATICS 380 420 3 50 NOTES 1 575 3 60APPLICATIONS FANMOTORS ARE460 3 60ANDARESUPPLIEDFROMEQUIPMENT MOUNTEDTRANSFORMER 2 FANCONTACTORS FANMOTORS FANPRESSURESWITCHES ANDFANTRANSFORMERS 575VONLY ARENOTUSED...

Page 11: ...11...

Page 12: ...Dimensions in mm Inlet Outlet Height Width Depth Weight Model Connections A B C Lb kg 1000 4 1 720 780 1250 4 85 2159 48 1207 49 1232 1 740 789 1500 4 1 850 839 1750 6 2 000 907 2000 6 2 100 953 2500...

Page 13: ...7 9 40 5 47 6 50 74 1 92 5 89 7 Branch Circuit Fuse Size amps 60 60 70 80 125 150 125 Watts 35 F Evaporator 100 F Ambient 8 480 9 860 12 140 12 780 18 960 22 100 25 640 Resistance ohms Three phase Tot...

Page 14: ...at trace air lines exposed to low ambients or dry air to lower dew point Install separator ahead of dryer See C below See C below See C below Check flow rate See C below Replace filter element Check f...

Page 15: ...38 31 G4130 138 31 G4130 138 31 G4130 138 31 G4130 138 31 High refrigerant Pressure switch G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 Fan cutout switch...

Page 16: ...ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAM...

Reviews: