background image

14

TROUBLESHOOTING GUIDE

1. Residual free moisture remaining in

downstream pipelines

2. Air bypass system is open
3. Inlet and Outlet connections are

reversed

4. Air lines downstream of dryer are

exposed to temperatures below the
dew point.

5. Excessive free moisture (bulk liquid) at

dryer inlet

6. Condensate not being drained
7. Dryer overloaded resulting in elevated

dew point.

8. Refrigeration system not  functioning

1. Excessive air flow
2. Freezing of moisture in evaporator

because of refrigeration system fault

3. Filter loaded with solid particulates

a. Power failure; open circuit
a. Compressor commanded off by

manual switch or programmed
schedule

b. Open circuit
c. Control circuit open on high or low

pressure cutout

Service interval specified has elapsed

a. Hot gas by-pass valve requires

adjustment

b. Low on refrigerant

a. Lack of condenser cooling

Air-cooled - Ambient temperature too
high, clogged condenser fins,
obstructed flow across condenser,
faulty fan motor or fan control
switch.
Water-cooled - Cooling temperature
too high, flow too low, clogged
strainer, faulty water regulating valve

a. Hot gas by-pass valve requires

adjustment

a. Dryer overloaded

b. Refrigeration system off or not

cooling sufficiently

a. Drain line restricted or frozen
b. Drain mechanism faulty

Dryer left in the Set Mode for longer
than 30 seconds

Blow out system with dry air

Check valve positions
Check for correct connection

Insulate or heat trace air lines exposed
to low ambients or dry air to lower
dew point
Install separator ahead of dryer

See C below
See C below

See C below

Check flow rate
See C below

Replace filter element

Check for power to dryer
Check current command status

Check power to compressor
Check display for fault

Perform scheduled service

Contact qualified technician or
manufacturer’s service department

Check air temperature 6” in front
of condenser
Clean condenser and check for free
air flow
Check fan and switch operation
Check cooling medium temperature
and flow, clean strainer, check
valve operation

Contact qualified technician or
manufacturer’s service department

Check compressed air flow,
temperature, and pressure
Check power to unit, power to
compressor, Low or High pressure
faults Have qualified technician
evaluate system

Open drain line
Turn 3-way valve handle so it points out
from the front of the unit. Open and
adjust the manual petcock in rear leg for
manual draining.
Rebuild drain mechanism.
Finish programing and press
Set/Run button

 

SYMPTOM

POSSIBLE CAUSE(S)

         CORRECTIVE ACTION

NOTE:  After fault correction, press reset button to clear display

A) Water downstream of dryer

B) High pressure drop across dryer

C) Checkpoint faults

1. Power on/off light
2. Compressor on light off

3. Alarm/Service alert light on -

check Display for active
conditions
SERVICE DRYER

LOW PRESSURE

HIGH PRESSURE
NOTE: If high refrigerant
pressure occurs, switch
must be manually reset

LOW TEMPERATURE
(also observed as low reading on
temperature indicator)

HIGH TEMPERATURE
(also observed as high reading
on temperature indicator)

DRAIN

TIME OUT

Summary of Contents for 9VXRD Series

Page 1: ...00 9VXRD3000 SERVICE DEPARTMENT 724 746 1100 INSTRUCTION MANUAL CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 9 ENGINEE...

Page 2: ...ge be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found...

Page 3: ...nches 610 mm of clearance in front of dryer E Standard units are designed to operate in ambients Air cooled 45 to 110 F 7 to 43 C Water cooled 45 to 130 F 7 to 54 C F Dryer is designed to operate at a...

Page 4: ...3 4 C At installation install the petcock on the bulkhead fitting for the manual drain For manual draining convenient dryer depressurization and EDD service a three way valve at the bottom of the mois...

Page 5: ...yer disconnect switch provided by others sec NEC 24 hours before refrigeration compressor is started Never use the disconnect switch to shut down the dryer for a extended period of time except for rep...

Page 6: ...restored after power interruption 7 To reinstitute SCHEDULE RUNNING If compressor is scheduled to be off push Set Run button to restart schedule If compressor is scheduled to be on push On Off button...

Page 7: ...edule Driven or Dryer Driven modes 1 De energize unit and disconnect the power supply to the dryer 2 Remove the cabinet panels as necessary to provide access to the Monitor panel 3 On the rear of the...

Page 8: ...t that must be removed is the upper shell cap Remove the insulation from the upper shell cap Check to be sure the unit is depressurized b Remove the two bolts on the upper shell coupling 3 and the upp...

Page 9: ...t 200 psig and 100 F ambient air temperature is 80 F and a 45 F dew point temperature is desired Answer 1 000 x 1 22 x 1 12 x 1 2 1 640 scfm TABLE 2 Air capacity correction factors Multipliers MODEL 1...

Page 10: ...ATICS 380 420 3 50 NOTES 1 575 3 60APPLICATIONS FANMOTORS ARE460 3 60ANDARESUPPLIEDFROMEQUIPMENT MOUNTEDTRANSFORMER 2 FANCONTACTORS FANMOTORS FANPRESSURESWITCHES ANDFANTRANSFORMERS 575VONLY ARENOTUSED...

Page 11: ...11...

Page 12: ...Dimensions in mm Inlet Outlet Height Width Depth Weight Model Connections A B C Lb kg 1000 4 1 720 780 1250 4 85 2159 48 1207 49 1232 1 740 789 1500 4 1 850 839 1750 6 2 000 907 2000 6 2 100 953 2500...

Page 13: ...7 9 40 5 47 6 50 74 1 92 5 89 7 Branch Circuit Fuse Size amps 60 60 70 80 125 150 125 Watts 35 F Evaporator 100 F Ambient 8 480 9 860 12 140 12 780 18 960 22 100 25 640 Resistance ohms Three phase Tot...

Page 14: ...at trace air lines exposed to low ambients or dry air to lower dew point Install separator ahead of dryer See C below See C below See C below Check flow rate See C below Replace filter element Check f...

Page 15: ...38 31 G4130 138 31 G4130 138 31 G4130 138 31 G4130 138 31 High refrigerant Pressure switch G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 Fan cutout switch...

Page 16: ...ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAM...

Reviews: