MINIMUM - MAXIMUM OPERATING CONDITIONS

Min.-Max. Inlet Air Pressure (compressed air at inlet to dryer)

30-200 psig (2.1-14 kgf/cm

2

)

Max. Inlet Air Temperature (compressed air at inlet to dryer)

120

°

F (49

°

C)

Min.-Max. Ambient Temperature

Air-cooled

45

°

F (7

°

C) - 110

°

F (43

°

C)

Water-cooled

45

°

F (7

°

C) - 130

°

F (54

°

C)

REFRIGERATION SYSTEM DATA

Compressor Type

Hermetic - Non-cycling

Refrigeration Compressor Horsepower

6

7.5

9

10

12

15

17.5

BTU/HR - Refrigeration Only @ 38

°

F PDP & 100

°

F Ambient

60 HZ

 47,060

 60,650

 70,590

 84,915

 94,120

 121,300

 141,180

50 Hz

 39,217

 50,542

 58,825

 70,763

 78,433

 101,083

 117,650

Outlet Air Temperature (nominal at rated conditions)

85

°

F (29

°

C)

Refrigerant Type

R-404A

Refrigerant Charge

See dryer serial number tag

Suction Pressure Setting

            (electric hot gas by-pass valve requires no adjustment)

Compressor Control Ranges (psig) (out-in)

High

450-348

Low

47-64

Condenser Fan Switch Setting (in-out)(psig)

 Fan 1

300-230

     (air-cooled models)

Fan 2

325-255

Air Flow Across Condenser (cfm) (air-cooled models)

60/50 Hz

2800/2330

4700/3920

4700/3920

4700/3920

5600/4670

9400/7835

11,200/9335

Condenser Cooling Water Requirements (water-cooled models)

     Recommended Water Pressure (psig)

40 min. - 120 Max*

     Gallons Per Minute of Flow Required with 85

°

F Cooling Water

60/50 Hz

15.1/12.6

18.7/15.6

24.4/20.3

25.5/21.2

32.2/26.4

40.7/33.9

44.2/36.8

     Inlet Water Connections

3/4”

1”

1-1/4”

ELECTRICAL

Nominal Voltage

208-230/3/60

Max.- Min. voltage

253-187

Rated Load Amps**

23.9

26

31.7

33.6

52.9

62.2

59.6

Locked Rotor Amps**

156

172

253

253

350

376

425

Minimum Circuit Ampacity

37.9

40.5

47.6

50

74.1

92.5

89.7

Branch Circuit Fuse Size (amps)

60

60

70

80

125

150

125

Watts @ 35

°

F Evaporator & 100

°

F Ambient

 8,480

 9,860

 12,140

 12,780

 18,960

 22,100

 25,640

Resistance (ohms)

Three phase (Total) (+/- 7%)

0.501

0.412

0.31

0.27

0.22

0.158-0.18

0.412 & 0.27

Nominal Voltage

460/3/60

Max. - Min. Voltage

506-414

Rated Load Amps**

9.3

11

13.8

14.9

25

27.6

25.9

Locked Rotor Amps**

70

90

118

118

158

178

208

Minimum Circuit Ampacity

15.6

17.7

21.2

22.6

35.4

42.5

40.2

Branch Circuit Fuse Size (amps)

20

25

35

35

60

70

60

Watts @ 35

°

F Evaporator & 100

°

F Ambient

 8,480

 9,860

 12,140

 12,780

 18,960

 22,100

 25,640

Resistance (ohms)

 Three phase (Total) (+/- 7%)

2.27

1.69

1.13-1.36

1.13-1.29

0.83

0.686-0.798

1.69&1.13-1.29

Nominal Voltage

575/3/60

Max. - Min. Voltage

632-518

Rated Load Amps**

7.9

9

10.9

12.2

20

22.1

21.2

Locked Rotor Amps**

54

62.3

96.5

96.5

125

143

158.8

Minimum Circuit Ampacity

13.8

15.3

17.5

19.2

29.3

35.2

34

Branch Circuit Fuse Size (amps)

20

20

25

30

45

50

50

Watts @ 35

°

F Evaporator & 100

°

F Ambient

 8,480

 9,860

 12,140

 12,780

 18,960

 22,100

 25,640

Resistance (ohms)

Three phase (Total) (+/- 7%)

3.56

2.54-2.87

1.76-2.02

1.76-2.02

1.28

1.07-1.30

2.54-2.87

&1.76-2.02

Nominal Voltage

380-420/3/50

Max. - Min. Voltage

462-342

Rated Load Amps**

9.3

11

13.8

14.9

25

27.1

25.9

Locked Rotor Amps**

70

90

118

118

151

174

208

Minimum Circuit Ampacity

16.1

18.1

21.6

22.9

35.7

42.2

40.8

Branch Circuit Fuse Size (amps)

25

25

35

35

60

60

60

Watts @ 35

°

F Evaporator & 100

°

F Ambient

 6,220

 7,210

 8,820

 9,280

 10,800

 14,600

 16,490

Resistance (ohms)

Three phase (Total) (+/- 7%)

2.27

1.69

1.13-1.36

1.13-1.29

0.83

0.686-0.798

1.69&1.13-1.29

* Allows continued operation with some restriction in the water strainer
** Compressor(s) only, air-cooled only
† For 208-230 ratings are for 230V input, for 380-420 ratings are for 400V input

ENGINEERING DATA

Summary of Contents for 9VXRD Series

Page 1: ...00 9VXRD3000 SERVICE DEPARTMENT 724 746 1100 INSTRUCTION MANUAL CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 9 ENGINEE...

Page 2: ...ge be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found...

Page 3: ...nches 610 mm of clearance in front of dryer E Standard units are designed to operate in ambients Air cooled 45 to 110 F 7 to 43 C Water cooled 45 to 130 F 7 to 54 C F Dryer is designed to operate at a...

Page 4: ...3 4 C At installation install the petcock on the bulkhead fitting for the manual drain For manual draining convenient dryer depressurization and EDD service a three way valve at the bottom of the mois...

Page 5: ...yer disconnect switch provided by others sec NEC 24 hours before refrigeration compressor is started Never use the disconnect switch to shut down the dryer for a extended period of time except for rep...

Page 6: ...restored after power interruption 7 To reinstitute SCHEDULE RUNNING If compressor is scheduled to be off push Set Run button to restart schedule If compressor is scheduled to be on push On Off button...

Page 7: ...edule Driven or Dryer Driven modes 1 De energize unit and disconnect the power supply to the dryer 2 Remove the cabinet panels as necessary to provide access to the Monitor panel 3 On the rear of the...

Page 8: ...t that must be removed is the upper shell cap Remove the insulation from the upper shell cap Check to be sure the unit is depressurized b Remove the two bolts on the upper shell coupling 3 and the upp...

Page 9: ...t 200 psig and 100 F ambient air temperature is 80 F and a 45 F dew point temperature is desired Answer 1 000 x 1 22 x 1 12 x 1 2 1 640 scfm TABLE 2 Air capacity correction factors Multipliers MODEL 1...

Page 10: ...ATICS 380 420 3 50 NOTES 1 575 3 60APPLICATIONS FANMOTORS ARE460 3 60ANDARESUPPLIEDFROMEQUIPMENT MOUNTEDTRANSFORMER 2 FANCONTACTORS FANMOTORS FANPRESSURESWITCHES ANDFANTRANSFORMERS 575VONLY ARENOTUSED...

Page 11: ...11...

Page 12: ...Dimensions in mm Inlet Outlet Height Width Depth Weight Model Connections A B C Lb kg 1000 4 1 720 780 1250 4 85 2159 48 1207 49 1232 1 740 789 1500 4 1 850 839 1750 6 2 000 907 2000 6 2 100 953 2500...

Page 13: ...7 9 40 5 47 6 50 74 1 92 5 89 7 Branch Circuit Fuse Size amps 60 60 70 80 125 150 125 Watts 35 F Evaporator 100 F Ambient 8 480 9 860 12 140 12 780 18 960 22 100 25 640 Resistance ohms Three phase Tot...