background image

6

3.

Manual Operation

a.

To manually turn the refrigeration system on or off
use 

On/Off

 button; Push 

Set/Run

 button to return

to schedule.

NOTE: After power interruption dryer will reenergize in Manual
override, refrigeration system off. To restart Schedule: (1) if
refrigeration system is scheduled to be off, Push 

Set/Run

button  (2) if refrigeration system is scheduled to be on, push

On/Off

  button, then 

Set/Run

 button.

C.

Starting dryer

IMPORTANT: Dryer must be energized 24 hours before
starting refrigeration compressor.

NOTE: It is recommended that dryer be started 15 minutes
before compressed air flow begins.

1.

On water-cooled models: after 24 hours, begin cooling
water flow.

2.

Check for  proper electrical voltage.

3.

Slowly pressurize unit air side by opening inlet isolation
valve. Check for leaks.

4.

After 15 minutes, open outlet isolation valve slowly.

5.

Close air by-pass valve.

6.

Dryer may be operated in Manual or scheduled modes.

NOTE: Check for correct phasing of unit. On air-cooled
models: check fan rotation (air must be pulled through the
condenser.) Fans may not start immediately or may cycle on
and off. If rotation is in the wrong direction follow the
procedure below. On water-cooled models: After starting
dryer if an unusual noise is heard and the discharge line does
not get hot, stop the dryer, reverse two power leads, restart,
and verify discharge line gets hot.

Manual mode - push 

On/Off

 button - refrigeration

compressor will start and run, green Compressor-on light
will illuminate. In this mode compressor will run continu-
ously and will not be turned on and off by the monitor.
MANUAL OVERRIDE will appear on interface panel.
Schedule mode - push 

Set/Run

 button.

SCHEDULE RUNNING will appear on the interface panel.
The refrigeration compressor will continue to be on or
off (as selected in the Manual Override Mode) until the
next scheduled event. The compressor will then turn on
or off as programmed.

NOTE: Schedule may be returned to the manual mode at any
time using the 

On/Off

  button. MANUAL OVERRIDE will appear

on interface panel. To reinstitute Schedule, push the 

Set/Run

button again.

NOTE: Restart after the power interruption. Unit will be in
MANUAL OVERRIDE mode, refrigeration compressor, off when
power is restored after power interruption.

7.

To reinstitute SCHEDULE RUNNING: If compressor is
scheduled to be off - push Set/Run button to restart
schedule. If compressor is scheduled to be on - push 

On/

Off

   button to manually start compressor, then push

the 

Set/Run

 button to restart schedule.

IMPORTANT: Dryer must be energized 24 hours before
refrigeration compressor is started

D.

Operating check points

1.

Check that green Power-on light is illuminated

2.

Check that green Compressor-on light is illuminated if
dryer is on in the manual mode or it is a scheduled on
time

IMPORTANT:  Refrigeration compressor must be restarted
after power interruption.

3.

Check interface panel

NOTE: Interface panel will switch between Current Time/
Operating Status screen and Hours to Service/Total
Operating Hours (HRS TO SVC/TOTAL) screen. TOTAL is
cumulative hours of refrigeration compressor operation.

a.

Verify that current time is correct

b.

Check HRS TO SVC: this indicates time remaining until
service is required; allow time for required
maintenance items to be ordered

c.

Check operating status:

MANUAL OVERRIDE - Dryer is either running
continuously (not being controlled by the scheduled
on/off times) or the refrigeration compressor has
been shut off using the 

On/Off

 button.

SCHEDULE RUNNING - Refrigeration compressor
is being turned on and off by the monitor per-
programmed schedule ( see B.2. to set schedule)

d.

Check Temperature indicator - indicator should read
in the green area

e.

Check Alarm/Service light If illuminated, check
Interface panel.

1)

If SERVICE DRYER appears, scheduled
maintenance time has elapsed (HRS TO SRV is 0).
Perform needed service and reset service
interval (see B.2.).

2)

If ALARM appears, a dryer fault is indicated; see
Troubleshooting Guide for possible remedies.
After fault correction push 

Reset

 button to turn

Fault alarm off.
Type of FAULTS:
LOW PRESSURE - the refrigeration compressor
control circuit has opened because of  low
suction pressure. Compressor will restart
automatically when fault is corrected.
HIGH PRESSURE - the refrigeration compressor
control circuit has opened because of high head
pressure. The high pressure switch must be
reset manually once the fault is corrected. Red
reset button is located on pressure switch inside
unit.
LOW TEMPERATURE - compressed air
temperature is below the set point

NOTE: If temperature probe is open, one light on left hand
side of Temperature indicator will be illuminated.

Summary of Contents for 9VXRD Series

Page 1: ...00 9VXRD3000 SERVICE DEPARTMENT 724 746 1100 INSTRUCTION MANUAL CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 9 ENGINEE...

Page 2: ...ge be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found...

Page 3: ...nches 610 mm of clearance in front of dryer E Standard units are designed to operate in ambients Air cooled 45 to 110 F 7 to 43 C Water cooled 45 to 130 F 7 to 54 C F Dryer is designed to operate at a...

Page 4: ...3 4 C At installation install the petcock on the bulkhead fitting for the manual drain For manual draining convenient dryer depressurization and EDD service a three way valve at the bottom of the mois...

Page 5: ...yer disconnect switch provided by others sec NEC 24 hours before refrigeration compressor is started Never use the disconnect switch to shut down the dryer for a extended period of time except for rep...

Page 6: ...restored after power interruption 7 To reinstitute SCHEDULE RUNNING If compressor is scheduled to be off push Set Run button to restart schedule If compressor is scheduled to be on push On Off button...

Page 7: ...edule Driven or Dryer Driven modes 1 De energize unit and disconnect the power supply to the dryer 2 Remove the cabinet panels as necessary to provide access to the Monitor panel 3 On the rear of the...

Page 8: ...t that must be removed is the upper shell cap Remove the insulation from the upper shell cap Check to be sure the unit is depressurized b Remove the two bolts on the upper shell coupling 3 and the upp...

Page 9: ...t 200 psig and 100 F ambient air temperature is 80 F and a 45 F dew point temperature is desired Answer 1 000 x 1 22 x 1 12 x 1 2 1 640 scfm TABLE 2 Air capacity correction factors Multipliers MODEL 1...

Page 10: ...ATICS 380 420 3 50 NOTES 1 575 3 60APPLICATIONS FANMOTORS ARE460 3 60ANDARESUPPLIEDFROMEQUIPMENT MOUNTEDTRANSFORMER 2 FANCONTACTORS FANMOTORS FANPRESSURESWITCHES ANDFANTRANSFORMERS 575VONLY ARENOTUSED...

Page 11: ...11...

Page 12: ...Dimensions in mm Inlet Outlet Height Width Depth Weight Model Connections A B C Lb kg 1000 4 1 720 780 1250 4 85 2159 48 1207 49 1232 1 740 789 1500 4 1 850 839 1750 6 2 000 907 2000 6 2 100 953 2500...

Page 13: ...7 9 40 5 47 6 50 74 1 92 5 89 7 Branch Circuit Fuse Size amps 60 60 70 80 125 150 125 Watts 35 F Evaporator 100 F Ambient 8 480 9 860 12 140 12 780 18 960 22 100 25 640 Resistance ohms Three phase Tot...

Page 14: ...at trace air lines exposed to low ambients or dry air to lower dew point Install separator ahead of dryer See C below See C below See C below Check flow rate See C below Replace filter element Check f...

Page 15: ...38 31 G4130 138 31 G4130 138 31 G4130 138 31 G4130 138 31 High refrigerant Pressure switch G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 Fan cutout switch...

Page 16: ...ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAM...

Reviews: