background image

 
 

Version 2, 31 October 2019, Page 

1

 of 

16

 

CliniMix

®

 CP-BS Inwall Thermo Progressive 

Shower Mixer with GalvinCare Handle W&C 

 

PRODUCT CODE: 

 

 

WM-TMVPMSCS 

 

TABLE OF CONTENTS 

1.0

 

INTRODUCTION 

1

 

2.0

 

TECHNICAL DATA 

2

 

3.0

 

SAFETY 

2

 

4.0

 

DESCRIPTION 

2

 

5.0

 

DIMENSIONS 

2

 

6.0

 

WATER SUPPLY CONDITIONS 

3

 

7.0

 

INSTALLATION 

3

 

8.0

 

OPERATION AND TESTING 

5

 

9.0

 

COMMISSIONING 

6

 

10.0

 

ISOLATE INLETS AND CLEAN FILTERS 

7

 

11.0

 

ADJUSTMENT OF THE MIX TEMPERATURE 

8

 

12.0

 

REMOVING AND INSPECTING MIXER CARTRIDGE 

9

 

13.0

 

MAINTENANCE 

10

 

14.0

 

DISINFECTION 

10

 

15.0 

 

TROUBLESHOOTING 

11

 

16.0 

 

WARRANTY 

12

 

 

 

1.0 

INTRODUCTION 

The CliniMix

®

 CP-BS Inwall Thermo Progressive ShowerMixer with GalvinCare Handle W&C is a high-performance 

thermostatic mixing valve suitable for a wide range of applications. The mixing valve has the following features: 

 

This progressive shower mixer provides state of the art features to comply with healthcare requirements. 

 

The GalvinCare

®

 paddle handle provides straight forward temperature control and minimises ligature risk. 

 

Suitable for high and low pressure systems with a thermostatically controlled water temperature of 48°C 
maximum. 

 

Enables water to be mixed closer to the point of discharge, minimising stagnant warm water which 
provides ideal conditions for legionella bacteria to grow. 

 

Smooth internal components and body reduces scale build-up and bacteria growth. 

 

Maximum temperature limiter fitted for protection from accidental scalding. 

 

Clean smooth lines facilitate fast and easy cleaning. 

 

All servicing and commissioning can be done without removing the device.  Easy access isolators, help 
minimise time spent on commissioning and maintenance. 

 

Designed to provide stable mixed temperature with rapid shut down in the event of cold or hot water supply 
failure. 

 

Approved to: AS/NZS 4032.4. 

IMPORTANT: All GalvinCare

®

 mental health taps are tested in accordance with AS/NZS 3718 and leave our 

premises in good working order.  Document to be read in conjunction with CliniMix

® 

Progressive Thermostatic Mixing 

Valve manual.

 

 
 
 

                        

          

Summary of Contents for CliniMix CP-BS

Page 1: ...s The GalvinCare paddle handle provides straight forward temperature control and minimises ligature risk Suitable for high and low pressure systems with a thermostatically controlled water temperature...

Page 2: ...e operation provided it is installed commissioned operated and maintained as per the recommendations outlined in this manual It should be noted however that this valve should not be considered as an a...

Page 3: ...cordance with the provisions of AS NZS 3500 Installations not complying with AS NZS 3500 may void the product and performance warranty provisions 7 0 INSTALLATION The CliniMix Thermostatic Progressive...

Page 4: ...s a split second it is still considered to be outside the operating conditions and may cause the valve to operate incorrectly In the event that this does occur measures must be taken to control the sp...

Page 5: ...Before tightening the flange make sure the handle fits correctly Put screws into flange and tighten finger tight the flange should still be able to move Slide the handle onto spline and move the flang...

Page 6: ...f the outlet temperature requires adjustment then follow the temperature adjustment in the installation instructions Shut Down Test Once the correct outlet temperature has been achieved the valves int...

Page 7: ...flow to stabilise for at least 15 seconds and record the temperature Quickly isolate the hot water supply to the valve The outlet flow should quickly reduce to be less than 0 4L min following the isol...

Page 8: ...a time to avoid the flange moving Refit handle 8 Fit the handle and fasten so the arrow shape on top of the handle matches the marking on the faceplate 11 0 ADJUSTMENT OF THE MIX TEMPERATURE 1 Set the...

Page 9: ...ove cartridge nut and check cartridge Unscrew cartridge and remove from body Check the cartridge for wear and damage Replace if required replacement cartridge available through your supplier Check and...

Page 10: ...mperature outlet then a 6 monthly servicing cycle may be adopted Otherwise servicing checks should be carried out more frequently e g every 4 months Follow the recommended maintenance procedures detai...

Page 11: ...aged Raise hot water temperature Clean the cartridge ensuring that all debris is removed Mix temperature unstable Flow rate below 2L min Thermostatic cartridge contains debris or is damaged Strainers...

Page 12: ...hat system must be in accordance with its m nuf turer s re mmend t n the C de nd re ev nt st tut ry nd t te r Terr t ry requ rements 4 The valve must be returned to Galvin Engineering together with a...

Page 13: ...Pressure ________kPa Cold Water Pressure _______kPa Make of Mixing Valve _______________________ Model No ________________________ Size _________ Valve Location Building ______________________________...

Page 14: ...k It is hereby certified that all the commissioning work has been carried out by the undersigned in accordance with the requirements of the Codes of Practice indicated prior Date of Valve Commissioned...

Page 15: ...f Warm Water C One Outlet in Use All Req d Outlets in Use One Outlet in Use All Req d Outlets in Use 1 2 3 4 5 6 7 8 9 10 11 Give details of brand and model designation Commensurate with the design fl...

Page 16: ..._______________________________Signature ______________________ Date _______________________ Maintenance Tests Yes Date of Previous Service ______________________________________________ Previous Serv...

Reviews: