15.0
TROUBLESHOOTING
PROBLEM
CAUSE
RECTIFICATION
The desired mixed water
temperature cannot be
obtained, or valve is
difficult to set.
−
Hot and cold supplies are fitted to
the wrong connections.
−
Thermostatic cartridge contains
debris or is damaged.
−
Strainers contain debris.
−
Non-return devices are damaged.
−
Refit the valve with hot/cold supplies fitted to
the correct connections.
−
Clean cartridge ensuring all debris is
removed and components are not damaged.
Replace if necessary.
−
Clean strainers of debris.
−
Check non-return device is not jammed.
−
Check for airlocks in the water supply.
The water temperature
selected is cold yet hot
water comes out.
−
Hot and cold water supply
connections are installed in reverse.
−
Refit the valve ensuring the hot/cold supplies
are fitted to the correct connections.
The thermostatic mixing
valve will not shut down.
−
The hot to mix temperature
differential is not 10°C or greater.
−
Thermostatic cartridge
contains debris or is damaged.
−
Non-return devices are damaged.
−
Raise hot water temperature.
−
Clean the cartridge ensuring that all debris is
removed.
Mix temperature
unstable.
−
Flow rate below 2L/min.
−
Thermostatic cartridge contains
debris or is damaged.
−
Strainers contain debris.
−
Non-return devices are damaged.
−
Rectify any pressure deterioration.
−
Clean the cartridge ensuring that all debris is
removed and components are not damaged.
Replace if needed.
−
Clean strainers ensuring debris is removed.
−
Check non-return device is not jammed.
Mix temperature
changing over time
−
Inlet conditions (pressure or
temperatures) are fluctuating.
−
Strainers contain debris
−
Install suitable pressure control valves
to
stabilise
inlet conditions.
−
Clean strainers ensuring debris is removed.
Either full hot or cold
flowing from outlet
fixture
−
Upper temperature ring is not
correctly set.
−
No flow from hot and cold supplies.
−
Damaged check valves.
−
Re-set temperature to between 35-46°C as
required.
−
Check water is switched on.
−
Replace faulty check valves.
Water is not flowing
from outlet.
−
Hot or cold water failure.
−
Thermostatic cartridge.
contains debris or damage
−
Strainers contain debris.
−
Restore inlet supplies and check mix
temperature.
−
Clean the cartridge ensuring that all debris is
removed and components are not damaged.
Replace if needed.
−
Clean strainers.