PEC Fuel Pump Fluid/Float Switch operation.
in
Apollo Dispensers
Software required:
LPG Apollo requires: Input Processor Assy = VI 1.21S (or >) This also allows for Single Temperature Probe
operation. Dip Switch # 2 @ SW3 set “ON”
Main Processor Assy = VA 2.30P (or >)
Apollo Std Petrol/Diesel Dispensers requires: Main Processor Assy = VA 2.30P (or >)
Hardware required:
LPG requires = Float Switch Assy. with Foam Extension added, & mounted as low as possible to base/floor of
Underground Sump Enclosure. Dip Switch #2 @ SW3 set “ON”
Apollo Std Petrol/Diesel Dispensers requires = Float Switch Assy mounted as low as possible to base/floor of
Underground Sump Enclosure (note: Link must be fitted @ position 10 on Display for Fluid operation)
Operation Description: (when Float is activated)
Dispenser with one side only operational (delivering)
Unused Side – Display shows “FLUId”
Side in uses – Dispenser shuts down immediately (including Valves & Motor) Display sit stationary showing
sale value.
Dispenser will begin to Beep after a period of 1 Min. if Nozzle in not returned then Beep
Once Nozzle is returned, Displays will then Flash until Nozzle is again removed, at this point Displays will then show
word “FLUId”
Refer to Resetting below.
Dispenser with both sides operational (delivering) (when Float is activated)
Both sides stop delivering immediately with Displays stationary displaying delivery values @ point when
delivery stopped.
Again Dispenser will start to Beep if Nozzles not returned within a Minute period.
Once Nozzle is returned, Displays with Flash until Nozzle is removed, Displays with then show “FLUId”
In both above cases Sale value remains on Console until sale is actioned/completed. Dispenser will also show on
Console as being Off Line
Dispenser Non operational (no delivery) (when Float is activated)
“FLUId will be displayed on both sides of Dispenser
Console Displays Dispenser as Off Line.
Refer to Resetting below.
Testing Float Switch Operation:
Testing can be conducted by manually lifting Float with wire Hook or similar. Display should show FLUId with
Dispenser going into Fatal error (Shut Down) Dispenser will require a Power shut down for a period of One Minute to Reset
Normal operation can then commence.
Resetting Dispenser Procedure
If FLUId is displayed @ Dispenser, Power to that unit should be immediately removed, with Isolating Switch locked out
to avoid being turned back on accidentally. Call Service Provider
Sump Enclosure should then be checked, removing Fluid present & source of leak repaired
Reconnect Power for Operation, should not need to reprogram if back up Battery still connected.
If pump Beeps: Hang up Nozzle.
If Displays Flash: Lift Nozzle then return to display Error
If Pump Off Line: Check for Error @ Pump (see above)
file @ gme c:/docum/pec/apollo2/float-desc.doc
23/02/01
Update: 01/03/01 02/04/02
Summary of Contents for Apollo 3000
Page 1: ...Apollo 3000 Set up Installation Parts Manual...
Page 2: ......
Page 4: ......
Page 15: ...11 Float Switch 89778 Float Swt Mtg Angle only 89749 Float Switch Bracket Assembly...
Page 26: ...22 Stage 1 Installation Procedure Sump Column Position Fig 2...
Page 27: ...23 file gme c docum pec apollo2 fig 2 manual doc Stage 1 Installation Service Area Spec Fig 3...
Page 28: ...24 Stage 1 Installation Procedure Mounting Positions Fig 4...
Page 29: ...25 Stage 3 Vent Box Installation Vent Box Position Sealing Spec Fig 5...