k Cod. 80004170 – 04.04.2018
PARAMETERS TABLE
Attention
: the access to the programming menus and the modification of the parameters are
exclusively reserved to installation and maintenance personnel. A wrong or improper modification of the
parameters can lead to malfunctions and/or to a lack of performances.
Cabinet type:
Giano R290
Gemini R290
Aries R290
Controller:
Dixell XR50CX
Defrost:
Hot gas
Release Tabella:
80004170 – 04.04.2018
Programmation Table:
80003980
Parametertabelle
Cod.
Type
Parameter description
u.o.m.
Range
Def.
SET
-
Set Point (valid only for stand-alone counters)
°C
LS÷US
2
Hy
Pr1
Differential (Hystheresis)
°C
0.1÷25.5
2
LS
Pr2
Minimum Set Point
°C
-50÷Set
-2
US
Pr2
Maximum Set Point
°C
Set÷110
10
ot
Pr1
Thermostat sensor calibration
°C
-12÷12
0.0
P2P
Pr1
Evaporator sensor presence
-
n÷Y
Y
oE
Pr2
Evaporator sensor calibration
°C
-12÷12
0
P3P
Pr2
Third sensor presence
-
n÷Y
N
o3
Pr2
Third sensor calibration
°C
-12÷12
0
odS
Pr2
Outputs delay at startup
min.
0÷255
2
AC
Pr1
Min. time between Compressor Off and successive start
min.
0÷50
4
rtr
Pr2
P1-P2 percentage for regulation (100=P1, 0=P2)
-
0÷100
80
CCt
Pr2
Continuous cycle duration
H
0÷24
0
CCS
Pr2
Set Point for continuous cycle
°C
-55÷150
4
Con
Pr2
Continuous ON time with faulty sensor
min.
0÷255
10
CoF
Pr2
Continuous OFF time with faulty sensor
min.
0÷255
10
CF
Pr2
Temperature measurement unit
-
°C÷°F
°C
rES
Pr1
Resolution (in=integer; de=decimal point)
-
In÷de
De
Lod
Pr2
Probe displayed
-
P1÷on
on
dLy
Pr2
Display temperature delay
Min.
0÷20
0
dtr
Pr2
with Lod=dtr, percentage of visualization betw. temp. P1 and P2
-
1÷99
99
tdf
Pr1
Defrost type (El=el.heater, in=hot gas)
-
El÷in
in
dFP
Pr2
Probe selection for defrost termination (nP,P1,P2,P3,P4)
-
-
P2
dte
Pr1
Defrost termination temperature
°C
-50÷50
7
idF
Pr1
Interval between defrost cycles
h
1÷120
4
MdF
Pr1
Maximum length of defrost
min.
0÷255
30
dSd
Pr2
Start defrost delay
min.
0÷99
0
dFd
Pr2
Displaying mode during defrost (rt, it, Set, DEF)
-
-
SET
dAd
Pr2
Max display delay after defrost
min.
0÷255
0
Fdt
Pr2
Draining time
min.
0÷120
5
dPo
Pr2
First defrost after startup (n=after idF, y=immed.)
-
n÷y
Y
dAF
Pr2
Defrost delay after fast freezing (0÷23h 50’)
-
-
0
ALC
Pr2
Temperature alarm config. (rE=related to Set, Ab=absolute)
-
rE÷Ab
rE
ALU
Pr1
Maximun temperature alarm
°C
Set÷110
10
ALL
Pr1
Minimum temperature alarm
°C
-50÷Set
5
AFH
Pr2
Differential for temperature alarm recovery
°C
0.1÷25.5
1
ALd
Pr2
Temperature alarm delay
min
0÷255
15
Summary of Contents for GIANO 70
Page 16: ...11 Cod 80000080c 17 07 2018...
Page 24: ...19 Cod 80001850 10 11 2014 X8 X8 X4 X4 X2 X2 4 5 6 7 8 9 10 11...
Page 25: ...20 Cod 80001850 10 11 2014 X8 X4 12 13 14...
Page 28: ...23 Cod 80002380a 04 08 2015 15 16 17 X2 18 X2 20 21 22 10 18 19...
Page 29: ...24 Cod 80002380a 04 08 2015 23 24 X2 26 X2 27 X2 28 24 27 25...
Page 45: ......
Page 46: ......
Page 47: ......