SERVICING, MAINTENANCE AND REFRIGERANT HANDLING
R290 is classified as
flammable refrigerant
of Class A3 according to ANSI/ASHRAE. It is a highly
flammable and very easy to ignite. It can burn with explosive impacts.
R290 in contact with air can cause a risk of fire or explosion in presence of
open flames
or
sparks
generated by electrical equipment
Servicing can be only performed by
qualified personnel
holding a valid certificate from an
accredited assessment authority which authorises:
- the competence to work on and break into a R290 refrigeration circuit
- the competence to handle refrigerants (including hydrocarbons) safely in accordance with the
EN13313:2011
Service intervention must be carried out considering the mentioned above risk:
do not use electric
tools and open flames
.
Components which require substitution: only use
original spare parts
for they have been
specifically approved for the use with this kind of refrigerant gas.
The refrigerant circuit is hermetically sealed (closed loop) therefore refrigerant filling, draining or
substitution of some components is
not possible without breaking the vacuum
. In such a case:
- the substitution
cannot be performed indoor
at the customer’s premises.
- the cabinet should be
moved to a controlled workshop environment
suitable for the type of
repair where work can be conducted safely.
- In any case, work in
confined spaces must be avoided.
Work area can be in the open or,
alternatively, must be properly ventilated
.
Ventilation should be able to safely disperse any
released refrigerant and expel it externally to the atmosphere.
While working on cabinet working with R290 during which the refrigerant can be possibly released
to the surrounding space, all possible
ignition sources
, including cigarette smoking, must be
reasonably far away from the place of installation, maintenance or disposal,
In case hot work is required (welding, brazing)
best practice must be applied
. This should require
the following procedure to avoid risk of fire or explosion.
-
remove refrigerant
-
purge the circuit (with inert gas)
-
evacuate
-
purge again with inert gas
-
open the circuit by cutting (or brazing)
Operator must be properly skilled and authorized to perform hot works on systems working with
flammable refrigerants.
For Split-Systems: In order to reduce flammability hazards the installation of this appliance must
only be carried out by a suitably qualified person.
Summary of Contents for GIANO 70
Page 16: ...11 Cod 80000080c 17 07 2018...
Page 24: ...19 Cod 80001850 10 11 2014 X8 X8 X4 X4 X2 X2 4 5 6 7 8 9 10 11...
Page 25: ...20 Cod 80001850 10 11 2014 X8 X4 12 13 14...
Page 28: ...23 Cod 80002380a 04 08 2015 15 16 17 X2 18 X2 20 21 22 10 18 19...
Page 29: ...24 Cod 80002380a 04 08 2015 23 24 X2 26 X2 27 X2 28 24 27 25...
Page 45: ......
Page 46: ......
Page 47: ......