e Cod. 80000230a – 01.12.2014
Alarm Recovery
Probe alarms
P1”, “P2”, “P3” and “P4” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Let the connections to be
checked by maintenance personnel before replacing the probe.
Temperature alarms
“HA”, “LA” “HA2” and “LA2” automatically stop as soon as the temperature returns to
normal values.
Alarms
“EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm
“CA” (with i1F=PAL) recovers only by switching off and on the instrument.
Attention:
in case of persisting warnings, caused by an alarm condition, inform the maintenance
personnel for a check of the equipment.
Other Messages
-
Pon
Keyboard unlocked
-
PoF
Keyboard locked
-
noP
in programming mode: none parameter is present in Pr1
in display mode (or dP2, dP3, dP4): the selected sensor is not enabled
-
noA
none alarm recorded