ESD5500E Series Speed Control Unit 9-2020-F  PIB1002

termInaL DefInItIon

noteS

A & B

Actuator (+/-)

16 AWG (1.3mm

2

) or larger wire

C & D

Magnetic Speed Pickup 

(D is ground)

• 

Wires must be twisted and/or shielded for their entire length

• 

Gap between speed sensor and gear teeth should not be smaller than 0.02 in. (.51mm)

• 

Speed sensor voltage needs to be at least 1 V RMS during crank

E & F

Battery Power (-/+)

• 

16 AWG (1.3mm

2

) or larger wire

• 

A 15 A fuse must be installed in the Positive battery lead to protect against reverse voltage

• 

Battery positive (+) input is Terminal F

G

Ground Signal

H

For 12 V systems with actuator currents above 5 A, may sometimes require a jumper between Terminals H and G

J

Variable Speed

5 kΩ resistive nominal. 

K & L

Droop Select

Active when closed

M

Idle Select

Close for Idle

N

Accessory Input

Load Sharing/Synchronizing, 0-10 V DC (5V Nominal, Reversed, 148 Hz/V). Shielded cabling recommended. 

P

Accessory Power Supply

10 V DC Output To Power GAC Load Sharing and Synchronizing Modules

When wiring ESD5500E Series controllers:
1.  Use shielded cable for all external connections to the ESD controller.
2.  One end of each shield, including the speed sensor shield, should be grounded to a single point on the ESD case.
3.  Terminal A, B, E,and F should be 16 AWG or larger. Long cables require increased wire size to minimize voltage drops. 
4.  Battery positive (+) Terminal F should be fused for 15 A. 
5.  Magnetic speed sensors Terminals C and D must be twisted and or shielded for the entire length. 
6.  The gap between the speed sensor and the ring gear teeth should be smaller than 0.02 in [0.5 mm] usually backing out 3/4 turn after 

touching ring gear teeth. Speed sensor voltage should be at lease 1 V AC RMS during cranking. 

7. 

If auto synchronization is used alone, not with a load sharing module, use a 3 Ω resistor between Terminal N and P to match the voltage 

between the speed control unit and the synchronizer. 

8.  When operating at the upper end of the control unit frequency range, add a jumper wire between Terminal G and J to increase the fre-

quency range of the control unit over 7000 Hz. 

9.  Terminal P is used to 10 V DC regulated supply to accessories. No more than 20 mA of current can be drawn from this supply. 

Ground reference is Terminal G. A short circuit in this terminal can damage the speed control unit.

4

WIRINg (CONTINUED)

An overspeed shutdown device, independent of the governor system, must be provided to prevent loss of 

engine control which may cause personal injury or equipment damage. Do not rely exclusively on the governor 

system to prevent overspeed. A secondary shutoff device such as a fuel solenoid must be used. 

aDDInG a PotentIometer

Use a single remote speed adjustment potentiometer to adjust engine 

speed. Select the desired speed range and the corresponding potenti-

ometer value. If the exact range is not found select the next higher range 

potentiometer.  Connect the potentiometer as shown in the potentiometer 

diagram.  

Summary of Contents for ESD5500E Series

Page 1: ...precisely in response to transient load changes The ESD5500E controls a wide variety of engines in isochronous or droop mode when connected to a proportional electric actuator and magnetic speed senso...

Page 2: ...rved ESD5500E Series Speed Control Unit 9 2020 F PIB1002 Mount in a cabinet engine enclosure or sealed metal box Vertical orientation allows fluids to drain in moist environ ments Dimensions Avoid Ext...

Page 3: ...ositive Terminal F should be fused for 15 A 5 Magnetic speed sensors Terminals C and D must be twisted and or shielded for the entire length 6 The gap between the speed sensor and the ring gear teeth...

Page 4: ...0E WD554 5 000 127 0 266 6 6 CW 1 031 26 OPTIONAL ACTUATOR CABLE SHIELDING TO MEET CE DIRECTIVE 5 750 146 5 000 127 5 500 140 A B C D E F G H J L M N P ACTUATOR PICK UP BATTERY AUX 10V OUTPUT C1 OFF O...

Page 5: ...FOR PROPER WIRING OF ACTUATOR BASED ON BATTERY VOLTAGE OPTIONAL ACTUATOR CABLE SHIELDING TO MEET CE DIRECTIVE 5 000 127 5 500 140 A B C D E F G H J L M N P ACTUATOR PICK UP BATTERY AUX 10V OUTPUT C1...

Page 6: ...WAM MA U S A ESD5500E WD554 Lead Circuit Soft Coupling Switch 1 C1 controls the Lead Circuit The normal position is ON Move the switch to the OFF position if there is fast instability in the system Sw...

Page 7: ...de range of droop is available with the internal control droop level requirements of 10 are unusual If droop levels experienced are higher or lower than those required contact GAC for assistance NOTE...

Page 8: ...bility of missed or extra pulses The speed control unit will govern well with 1 0 V RMS speed sensor signal A speed sensor signal of 3 V AC or greater at governed speed is recommended Measurement of t...

Page 9: ...V DC then check for actuator binding linkage binding If the voltage reading is below 0 8 V DC Defective speed control unit Actuator does not energize fully 1 Measure the voltage at the battery while...