G-U RZ 25 Installation And Operating Instructions Manual Download Page 20

20

EN

RWA compact control unit

Installation and operating instructions

RZ 25 | RZ 50 | RZ 75

12.2015 | G31553 | Designed in Germany

Relay for status retransmission to external systems.
Alarm

Change-over contact, 3-pin

The relay switches if an RWA alarm is applied (with mains supply or emergency power supply).
The source of the alarm is the triggering of a manual or automatic signalling device.

Error

Change-over contact, 3-pin

The relay is enabled in the idle state (no error). If an error or power failure occurs, the relay drops 
out.

Errors are all special statuses that are indicated by the LEDs and prevent manual interventions or 
correct operation of the system.

Status

Wiring connections

No alarm

Terminals 42 and 62 are connected

Alarm

Terminals 42 and 52 are connected

Status

Status of relay

Wiring connections

Idle state (no error)

Relay is enabled

Terminals 41 and 51 are connected

Fault

Relay drops out

Terminals 41 and 61 are connected

4.3.1  Retransmission of statuses

Retransmission of alarm / error - only RZ 50 / RZ 75

Connection of weather station

COM
NO

4.3.2  Networking of control units

In order to increase the power output or extend the ventilation lines, up to fi ve RWA compact 
control units of any type can be connected together.

Summary of Contents for RZ 25

Page 1: ...0 46003 IA 0 EN 02 12 2015 G31553 Designed in Germany WINDOW TECHNOLOGY RZ 25 RZ 50 RZ 75 RWA compact control unit Installation and operating instructions EN...

Page 2: ...cable cross section and length Page 12 3 5 1 Calculation of cable cross section with drives of the same type Page 12 3 5 2 Calculation of cable cross section with di erent drives Page 12 3 6 Mounting...

Page 3: ...c ventilation CLOSE Page 31 6 2 5 Weather control Page 31 6 3 Alarm Page 32 7 Maintenance and cleaning Page 32 7 1 Safety instructions for maintenance and cleaning Page 32 7 2 Maintenance Page 32 7 3...

Page 4: ...from external components is not applied Verify that the system is safely isolated from the power supply Regulations for installation and assembly RWA compact control units may only be tted installed r...

Page 5: ...d use According to the obligations de ned in the German Product Liability Act 4 ProdHaftG to be met by a manufacturer in relation to his products the following information in these instructions must b...

Page 6: ...and heat exhaust ventilation function according to prEN 12101 9 and EN 12101 10 i e 72 hrs operational readiness Ventilation functions with time control Ventilation functions with weather control Cen...

Page 7: ...ories Scope of delivery RWA compact control unit RZ 25 K 18328 00 0 RWA compact control unit RZ 50 K 18329 00 0 RWA compact control unit RZ 75 K 18433 00 0 consisting of Compact control unit pre mount...

Page 8: ...tructions on page 4 without fail prior to assembly and installation DANGER 3 2 Layout of compact control unit 2 4 3 1 1a a b c g e d f Layout of compact control unit RZ 25 Components 1 Housing 1a Prot...

Page 9: ...ow 8 A slow blow 8 A slow blow 2 4 3 a b 1 1a c e d g f Layout of compact control units RZ 50 RZ 75 Components 1 Housing 1a Protective conductor terminal in the housing 2 Power supply unit 3 Batteries...

Page 10: ...5 A Total current 6 0 A 0 25 A 6 25 A Selected control unit RZ 50 with a max interrupting current of 6 5 A Compact control unit Max output current Nominal current Breaking current RZ 25 2 5 A 3 2 A RZ...

Page 11: ...ion of motor 3 Ventilation 1 5 mm J Y ST Y 4x2x0 8 400 m 4 RWA Fire Button 1 5 mm JE H St H FE 180 E30 4x2x0 8 400 m 5 Sensor in 1 5 mm JE H St H FE 180 E30 2x2x0 8 400 m 6 Wind Rain 1 5 mm NYM O 5 7...

Page 12: ...d Min cable cross section mm Single cable length m x number of drives Factor fdrive Cable cross section mm x factor fdrive Number of drives Drive 300 24 S 24 L K25 K30 K35 K60 RWA1050 S80 TA60 RWA1000...

Page 13: ...unit on page 13 Insert the hexagon head screws provided into the four holes in the housing of the RWA compact control unit and screw the housing to the base plate of the IP mounting kit Only use the...

Page 14: ...rained electrical specialist 4 2 Connection of power supply 4 2 1 Establishing the power supply Take out the power supply unit by removing the fixing screw at the terminal clamps of the power supply u...

Page 15: ...ntrol unit may be damaged Insert the provided batteries at an angle by their protruding tab and press them into the housing without exertion of force Figure page 16 Fasten the batteries in the housing...

Page 16: ...EN RWA compact control unit Installation and operating instructions RZ 25 RZ 50 RZ 75 12 2015 G31553 Designed in Germany Connection of batteries RZ 25 RZ 50 RZ 75 Power supply unit Battery 2 Battery...

Page 17: ...eatdetectorWMD3 10 k Smoke detector Smoke detector When connecting an automatic signalling device the terminal resistor between terminal clamps SI1 and SI2 must be removed and installed in the last au...

Page 18: ...HSE RWA Fire Button 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 www g u com www g u com RE RE RA RA OK OK 1 2 3 4 8 3 7 2 1 5 4 5 7 8 1 1 5 5 2 2 6 6 3 3 7 7 4 4 8 8 Remove the resistor RE in all HSE push button...

Page 19: ...F ZU RE RA Remove the resistor RE in all HSE push buttons apart from the last HSE push button in the line The resistor RE must not be removed from the last HSE push button in the line Maximum of 10 RW...

Page 20: ...ops out Errors are all special statuses that are indicated by the LEDs and prevent manual interventions or correct operation of the system Status Wiring connections No alarm Terminals 42 and 62 are co...

Page 21: ...r supply network interface modules are not required NOTE The line termination resistors must be applied at the last control unit of the bus in each case via jumper J2 apply jumper at the rst and secon...

Page 22: ...d on the BKS NET bus and their addresses set via a jumper see the data sheet enclosed with the IO10 ST20 IO10 4 3 2 3 Connection of control units Observe the safety instructions for bringing the BKS N...

Page 23: ...adress 2 Input Contact Function 1 I1 Rain 2 I2 Wind 3 I3 Timer edge triggered 4 I4 No function Output Contact Function 1 R1 41 51 61 Rain 2 R2 42 52 62 Wind 3 R3 43 53 63 RWA push button pressed 4 R4...

Page 24: ...ctric shock Read the safety instructions in chapter 1 2 Safety instructions on page 4 without fail before taking into operation DANGER Signalling Designation Display at LED Functional description LED...

Page 25: ...ng Designation Display at LED Functional description LED Operating LED ON Window open Flashing Drive moving OFF Window close ST20 Signalling Designation Display at LED Functional description LED green...

Page 26: ...ed in Germany 5 2 2 Internal displays and operating elements Push buttons DIP switch potentiometers change over running direction of motors jumper Position Element 1 Emergency close reset push button...

Page 27: ...ive ON Rain LED 7 H7 green Motor actuation OPEN OFF No actuation Flashing 0 5 Hz Line interruption Flashing 2 Hz Line short circuit Flashing 5 Hz Motor line fuse defective ON Actuation in OPEN directi...

Page 28: ...owledge errors and close drives When changing over the running direction drives close in the event of an RWA alarm the drives remain closed following the reset Changeover of running direction in the e...

Page 29: ...other control units on the bus The other control units max 4 that are connected on the bus automatically become bus slaves Start up procedure for function slaves Wire the LA and LB cables of the compa...

Page 30: ...ing damage close the drives when the CLOSE in the event of power failure function is active To activate the CLOSE in the event of a power failure function put switch 1 in the ON position 6 2 3 Runtime...

Page 31: ...tch 2 in the OFF position 6 2 5 Weather control Rain The purpose of the rain input is to connect an external rain sensor or weather station If the input contact is closed the drives close for safety r...

Page 32: ...ation of the RESET button in the compact control unit Actuation of the reset button in the manual signalling device RWA push button HSE Reset pulse at the corresponding input in the IO10 module Acoust...

Page 33: ...pact control units to their delivery condition as described below Apply jumper J1 Press the reset button for 25 s after 5 s visual con rmation is provided that the bus settings have been reset Remove...

Page 34: ...es 9 1 Directives In order to ensure reliable operation of the systems a recognized quality management system to EN ISO 9001 2000 is used during production This system has been type tested by T V Th r...

Page 35: ...35 9 2 T V Th ringen certi cate...

Page 36: ...ys in pairs Check the wiring of the batteries and repair Check fuses F2 and F3 in the compact control unit see page 9 and replace if necessary H6 Flashing 1 Hz Rain detector external weather station T...

Page 37: ...line The fuse of the manual alarm line has tripped Test the wiring and connections of the manual alarm line and repair The fuse resets itself automatically H11 Brief ashing Bus LED At least one contr...

Page 38: ...38 EN RWA compact control unit Installation and operating instructions RZ 25 RZ 50 RZ 75 12 2015 G31553 Designed in Germany...

Page 39: ...39...

Page 40: ...Errors and omissions reserved Subject to technical modi cations Editor Gretsch Unitas GmbH Baubeschl ge Johann Maus Str 3 D 71254 Ditzingen Tel 49 0 7156 301 0 Fax 49 0 7156 301 293 www g u com...

Reviews: