39
SYSTEM CONFIGURATION
Inclusion of a UPS in a parallel system does not require particular configurations; however, it is possible to modify the whole
system configuration as follows.
Before starting the configuration modification process verify that the menu “8.CONFIGURATION” (or any of its
sub-menus) is not active on any UPS.
C
ONFIGURATION PROCEDURE
MODIFICATION FROM CONTROL PANEL
The modification is communicated and executed automatically by all the system units only after exiting from menu 8
(Configuration).
MODIFICATION THROUGH CONFIGURATION SOFTWARE
The modification is communicated and executed by all the units at the configuration update.
C
OMMON BATTERY CONFIGURATION
If a battery box common to all units is used, the parallel system must be configured with the configuration software provided to
service centers. From the menu “Battery expansion” select option “Parallel common battery” and specify in the “External battery”
box the rated capacity of the battery box in Ah (refer to the figure below).
Battery menu
The “Internal battery” field shows the specified rated capacity of the batteries of each UPS.
If the common battery box is equipped with a battery charger the rated charge value in A must be entered in the “Additional
charger” field.