60-G 1/01
Problem
Cause
Remedy
Flame Failure
5. Flame Rod Adjustment
Check flame rod for carbon buildup and clean if
or UV Scanner
necessary. Check flame rod adjustment via a
display module. Flame signal should be 5 VDC.
Check for cracks in porcelain. If found, replace.
Check for dirt on flame scanner and clean.
Check for proper location of detector.
6. Flame Safeguard Control
Check voltage at terminal leading to main gas valve.
If no power, replace the control.
7. Loose wire at fuel
Tighten wiring connections.
valve circuit
8. Contact open on air
Adjust to proper setting.
safety switch
9. Scanner wiring reversed
Change to correct terminals.
at panel box.
Burner Cut-Off
1. Power Supply
Check fuse or circuit; reset or replace, as necessary.
2. Gas Supply
Check to be sure main gas cock is not closed. Check coil
in gas valve with OHM meter. Replace if faulty. Check gas
regulator setting and readjust as necessary. Check inlet
gas pressure and increase or decrease as necessary.
3. Ignition Electrodes
Check electrodes for carbon buildup and clean if
necessary. Check for proper adjustment Readjust if
necessary. Check for cracks in porcelain; if found replace.
4. Flame Rod Adjustment
Check flame rod for carbon buildup and clean if
or UV Scanner
necessary. Check flame rod adjustment via a
display module. Flame signal should be 5 VDC.
Check for cracks in porcelain. If found, replace.
Check for dirt on flame scanner and clean.
Check for proper location of detector.
5. Air Switch
Check for bad air switch by jumpering the two air switch
leads at the terminal block. If the boiler starts and runs
with these terminals jumpered, the air switch should
be replaced.
6. Gas Valve Sticking
Check for dirt in valve or orifice and clean if necessary.
(Pilot)
Check for faulty actuator or valve and replace if necessary.
7. Weak Ampl;ifier
Replace.
8. Weak Pilot
Adjust to larger pilot by adjusting pilot gas pressure
regulator.
9. Faulty Liquid Level Control Check to see if there is power to terminal number 10
when the sight glass shows the proper water level.
If there is no power at this terminal, the control is bad and
must be replaced.
10. Dirty or defective
Clean or replace.
UV Scanner.
Maintenance
Summary of Contents for FB-A 10
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ...2 G 1 01...
Page 9: ...Safety Warnings Precautions 1 3 G 1 01...
Page 10: ...4 G 1 01...
Page 12: ...6 G 1 01...
Page 13: ...7 G 1 01 Description Instructions LE...
Page 14: ...8 G 1 01...
Page 17: ...11 G 1 01 Operation LE...
Page 18: ...12 G 1 01...
Page 20: ...14 G 1 01...
Page 21: ...15 G 1 01 Maintenance LE...
Page 22: ...16 G 1 01...
Page 29: ...23 G 1 01 Parts LE...
Page 30: ...24 G 1 01...
Page 32: ...26 G 1 01...
Page 33: ...Boiler Description Instructions Gas Fired Boiler 2 27 G 1 01...
Page 37: ...30 G 1 01 Description Instructions I E K K J K D C H B A G F...
Page 50: ...42b G 1 01...
Page 51: ...43D G 1 01 Operation 3...
Page 52: ...43b G 1 01...
Page 59: ...Maintenance 4 5 G 1 01...
Page 60: ...51 G 1 01...
Page 73: ...Parts 5 6 G 1 01...
Page 88: ...79 G 1 01 Parts...
Page 90: ...81 G 1 01 Parts Gas Burner Ignition Assembly Gas Burner Components...
Page 95: ...Warranty 6 8 G 1 01...
Page 96: ...87 G 1 01...
Page 98: ...89 G 1 01...
Page 100: ...91 G 1 01...
Page 101: ...Component Data Sheets 7 G 1 01...
Page 102: ......