7. Additional charge calculation
7-1. Model: AOHG72LRLA
Refrigerant type
R410A
Factory charge amount
g
5,600
¢
Refrigerant charge
Total pipe length m
30 or
less
40
50
60
70
80
90
100
(Max.)
110 g/m
Additional
charge amount
g
0
1,100
2,200
3,300
4,400
5,500
6,600
7,700
7-2. Model: AOHG90LRLA
Refrigerant type
R410A
Factory charge amount
g
7,100
¢
Refrigerant charge
Total pipe length m
30 or
less
40
50
60
70
80
90
100
(Max.)
110 g/m
Additional
charge amount
g
0
1,100
2,200
3,300
4,400
5,500
6,600
7,700
- 63 -
OUTDOOR UNIT
AOHG72-90LRLA