5-2. Heating capacity
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
¢
Model: ARHG72LHTA
AFR
m
3
/h
4,300
Indoor temperature
°CDB
16
18
20
22
24
Outdoor temperature
°CDB
°CWB
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
kW
kW
kW
kW
kW
-20
-21
10.58
5.57
10.32
5.68
10.07
5.80
9.82
5.91
9.57
6.02
-15
-16
16.21
6.42
15.83
6.56
15.44
6.69
15.06
6.82
14.68
6.96
-10
-11
18.89
6.82
18.44
6.96
18.00
7.10
17.55
7.25
17.10
7.39
-5
-7
20.98
7.11
20.48
7.26
19.98
7.41
19.48
7.56
18.99
7.70
0
-2
22.62
7.19
22.08
7.34
21.54
7.49
21.00
7.63
20.47
7.78
5
3
25.56
7.20
24.95
7.35
24.35
7.50
23.73
7.64
23.13
7.79
7
6
25.83
7.21
25.22
7.36
24.60
7.51
23.99
7.66
23.37
7.81
10
8
27.04
7.16
26.39
7.30
25.74
7.46
25.09
7.60
24.46
7.76
15
10
28.06
7.16
27.39
7.30
26.72
7.45
26.05
7.61
25.38
7.71
20
15
25.25
6.25
24.64
6.37
24.04
6.50
23.44
6.64
22.83
6.72
24
18
25.81
6.21
25.19
6.33
24.58
6.47
23.96
6.61
23.35
6.69
¢
Model: ARHG90LHTA
AFR
m
3
/h
4,300
Indoor temperature
°CDB
16
18
20
22
24
Outdoor temperature
°CDB
°CWB
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
kW
kW
kW
kW
kW
-20
-21
12.77
6.65
12.47
6.79
12.16
6.93
11.86
7.07
11.56
7.19
-15
-16
19.57
7.68
19.11
7.84
18.64
8.00
18.18
8.16
17.72
8.31
-10
-11
22.81
8.16
22.27
8.32
21.73
8.49
21.19
8.66
20.65
8.83
-5
-7
25.33
8.50
24.73
8.68
24.12
8.86
23.52
9.03
22.92
9.21
0
-2
27.31
8.59
26.66
8.77
26.00
8.95
25.35
9.13
24.71
9.29
5
3
30.86
8.61
30.12
8.79
29.39
8.97
28.65
9.13
27.92
9.27
7
6
31.19
8.62
30.44
8.80
29.70
8.98
28.96
9.16
28.22
9.28
10
8
32.64
8.56
31.86
8.73
31.08
8.92
30.29
9.09
29.53
9.28
15
10
33.88
8.56
33.07
8.72
32.26
8.91
31.45
9.10
30.65
9.22
20
15
30.48
7.47
29.75
7.61
29.02
7.77
28.30
7.94
27.57
8.04
24
18
31.16
7.43
30.42
7.57
29.67
7.73
28.93
7.90
28.20
8.00
DESIGN & TECHNICAL MANUAL
- 10 -
DUCT TYPE
ARHG72-90LHTA
Summary of Contents for GENERAL ARHG72LHTA
Page 5: ...Part 1 INDOOR UNIT DUCT TYPE ARHG72LHTA ARHG90LHTA ...
Page 12: ...4 2 Model ARHG90LHTA I O PCB WLAN adapter Converter etc 8 DUCT TYPE ARHG72 90LHTA ...
Page 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOHG72LRLA AOHG90LRLA ...
Page 64: ...5 Wiring diagrams 5 1 Models AOHG72LRLA and AOHG90LRLA 60 OUTDOOR UNIT AOHG72 90LRLA ...