10-1. External input
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor
unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
1
2
Terminal
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
¢
External input and output PCB
The indoor unit Operation/Stop can be set by using the input terminal on the PCB.
Input select
Use either one of these types of terminals according to the application. (Both types of termi-
nals cannot be used simultaneously.)
• Dry contact
In case of internal power supply, set the slide switch of SW1 to "NON VOL" side.
1
2
C
Input 1
Input 2
PCB
Connected unit
+
+
-
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
• Apply voltage
In case of external power supply, set the slide switch of SW1 to "VOL" side.
1
2
C
Input 1
Input 2
Power supply
PCB
Connected unit
+
-
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
*2: Make the power supply DC 12 V to 24 V 10 mA or more.
DESIGN & TECHNICAL MANUAL
- 22 -
DUCT TYPE
ARHG72-90LHTA
Summary of Contents for GENERAL ARHG72LHTA
Page 5: ...Part 1 INDOOR UNIT DUCT TYPE ARHG72LHTA ARHG90LHTA ...
Page 12: ...4 2 Model ARHG90LHTA I O PCB WLAN adapter Converter etc 8 DUCT TYPE ARHG72 90LHTA ...
Page 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOHG72LRLA AOHG90LRLA ...
Page 64: ...5 Wiring diagrams 5 1 Models AOHG72LRLA and AOHG90LRLA 60 OUTDOOR UNIT AOHG72 90LRLA ...