2-19. E: 86. High pressure switch error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
8 time flash
Timer indicator
6 time flash
Economy indicator
Continuous flash
Error code
E: 86
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator
Outdoor unit main PCB
When pressure switch open is detected in 10 seconds
after the power is turned on.
High pressure switch
Forecast of cause
High pressure switch connector disconnection or open
High pressure switch characteristics failure
Main PCB failure
Check point 1. Check the high pressure switch connection state
•
Check connector and wiring connection state.
•
Check if cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Check the high pressure switch characteristics
•
Check switch characteristics.
For the characteristics of the high pressure switch, refer to below.
↓
Check point 3. Replace main PCB
Change main PCB and check operation again.
↓
End
• Type of contact
C
H
Pressure
• Characteristics of pressure switch
Pressure switch 1
Contact: Short → Open
4.2±0.1 MPa
Contact: Open → Short
3.2±0.15 MPa
30/36 model: P770
2-19. E: 86. High pressure switch error (Outdoor unit)
- (03-24) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General AOHH30KMTB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Page 36: ......
Page 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Page 94: ......
Page 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...