![Fujitsu General AOHH30KMTB Service Manual Download Page 147](http://html.mh-extra.com/html/fujitsu/general-aohh30kmtb/general-aohh30kmtb_service-manual_2343870147.webp)
¢
External Input and Output PCB
• A twisted pair cable should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V±2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to
"Setting of external input and output"
•
When indicator or other components are connected directly:
Example:
Rotary SW on External Input and Output PCB is set to “1”.
1
2
CN310
LED 1
(Operation status)
PCB
Resistor
Connected device
+
-
1
2
CN311
LED 2
(Error status)
Resistor
+
-
1
2
CN312
LED 3
(Indoor unit fan
operation status)
Resistor
+
-
•
When connecting with a device equipped with a power supply:
Example:
Rotary SW on External Input and Output PCB is set to “1”.
1
2
Connected device 1
CN310
PCB
Connected device
Relay
(Operation status)
-
+
1
2
Connected device 2
CN311
(Error status)
-
+
1
2
Connected device 3
CN312
(Indoor unit fan
operation status)
-
+
3-2. External output
- (05-17) -
3. External input and output (For indoor unit)
FIELD
WORKING
FIELD
WORKING
Summary of Contents for General AOHH30KMTB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Page 36: ......
Page 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Page 94: ......
Page 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...