2-13. E: 65. Trip terminal L error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
6 time flash
Timer indicator
5 time flash
Economy indicator
Continuous flash
Error code
E: 65
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator
Outdoor unit
Main PCB
When the signal from FO terminal of IPM is “L” (0 V)
during the compressor stopping.
Forecast of cause
Main PCB failure
Check point 1. Check main PCB
Replace the outdoor unit main PCB.
↓
End
2-13. E: 65. Trip terminal L error (Outdoor unit)
- (03-18) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING