NOTES:
• The air conditioner custom code is set to prior to shipment.
• If you do not know the air conditioner custom code setting, try each of the custom codes ( →
→ → ) until you find the code that operates the air conditioner.
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.
Functions
1)
11
Filter sign
2)
30/31
Room temperature control for indoor unit sensor
3)
35/36
Room temperature control for wired remote controller sensor
4)
40
Auto restart
5)
42
Room temperature sensor switching
6)
44
Remote controller custom code
7)
46
External input control
8)
48
Room temperature sensor switching (Aux.)
9)
49
Indoor unit fan control for energy saving for cooling
10)
60
Switching functions for external output terminal
11)
96
Special cooling operation
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (400 hours)
01
Long interval (1,000 hours)
02
Short interval (200 hours)
03
No indication
♦
1-1. Function settings by using remote controller
- (05-2) -
1. Function settings (For indoor unit)
FIELD
WORKING
FIELD
WORKING
Summary of Contents for General AOHH30KMTB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Page 36: ......
Page 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Page 94: ......
Page 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...