7-16. Unit status monitoring and the detected value indication
The wired remote controller can monitor the indoor and outdoor units' status and display the detect-
ed result as a relevant ID.
For details of the display method, refer to the Chapter of “Display Sensor Values” in the
Installation
Manual
of Wired Remote Controller (Touch Panel).
The status can be monitored and displayed on the wired remote controller by assigning an arbitrary
ID. For available ID list, refer to the table below.
NOTE:
Operating time for each part cannot be reset when the part is replaced. Take notes of the
operating time before replacing to count the operating time of the replaced part.
Available Sensor ID
Sensor ID
Item
Unit
Remarks
00: Indoor unit
00
000
Suction temp.
01: °C or °F
00
001
Room temp.
01: °C or °F
When the wired remote controller
thermistor is enabled, temperature of
the wired remote controller thermistor
is displayed.
00
002
Wired remote controller detected
temp.
01: °C or °F
00
006
Heat exchanger middle temp.
01: °C or °F
00
020
Fan rotation number
03: rpm
00
080
Indoor unit total energized hours
11: h
00
081
Total filtering hours
11: h
00
082
Indoor unit fan total operation hours
11: h
00
095
Presence or absence detected by
human sensor
00: —
0: Absence, 1: Presence
—: Human sensor error or No human
sensor
00
140
Operation or Stop (External input)
00: —
0: Off, 1: On
—: When the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
142
Forced stop (External input)
00: —
0: Off, 1: On
—: When the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
143
Operation or Stop 2 (External input)
00: —
0: Off, 1: On
—: When the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
155
Operation or Stop On/Off (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
156
Error On/Off (External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
157
Indoor unit fan interlocking On/Off
(External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
7-16. Unit status monitoring and the detected value indication
- (04-28) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General AOHH30KMTB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Page 36: ......
Page 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Page 94: ......
Page 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...