Heating mode
F zone
7°C
E zone
2°C
D zone
-7°C
C zone
B zone
A zone
-10°C
-15°C
G zone
12°C
H zone
16°C
I zone
20°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOHG45KRTA
AOHG54KRTA
A zone
46 rps
B zone
42 rps
C zone
35 rps
D zone
32 rps
E zone
23 rps
F zone
20 rps
G zone
17 rps
H zone
13 rps
I zone
16 rps
1-5. Rotation number of compressor limitation by outdoor temperature
- (04-5) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General AOHG45KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Page 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Page 36: ......
Page 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Page 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...