Available Sensor ID
Sensor ID
Item
Unit
Remarks
00
162
External output command by remote
controller (External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
163
Set-point temp. not reached in server
room function On/Off (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
174
Anti-freeze protection On/Off
00: —
0: Off, 1: On
01: Outdoor unit
01
000
Outdoor temp.
01: °C or °F
01
001
Discharge temp.
01: °C or °F
01
002
Suction temp.
01: °C or °F
01
003
Heat exchanger middle temp.
01: °C or °F
01
004
Heat exchanger outlet temp.
01: °C or °F
01
005
Liquid pipe temp. (Before expansion
valve)
01: °C or °F
01
006
Liquid pipe temp. 2 (After expansion
valve)
01: °C or °F
01
007
Compressor temp.
01: °C or °F
01
008
Heat sink temp.
01: °C or °F
01
009
Liquid pipe temp. 3 (Sub cool heat
exchanger inlet)
01: °C or °F
01
010
Liquid pipe temp. 4 (Sub cool heat
exchanger outlet)
01: °C or °F
01
011
2-way valve temp. (For multi-split
type)
01: °C or °F
01
012
3-way valve temp. (For multi-split
type)
01: °C or °F
01
040
Discharge pressure
02: MPa
01
041
Suction pressure
02: MPa
01
042
Gas pipe pressure for outdoor unit
02: MPa
01
050
Fan 1 rotation number
03: rpm
01
051
Fan 2 rotation number
03: rpm
01
055
Compressor rotation number
04: rps
01
060
Expansion valve (Upstream during
heating)
05: pls
01
061
Expansion valve 2 (Downstream
during heating)
05: pls
01
062
Expansion valve 3 (For sub cool heat
exchanger)
05: pls
01
063
Expansion valve 4 (For injection)
05: pls
01
064
Expansion valve 5 (For multi-split
type)
05: pls
01
075
Solenoid valve (For injection)
06: Open/Close 0: Close, 1: Open
01
080
4-way valve output status
07: Cooling/
Heating
0: Cooling, 1: Heating
01
085
Pressure switch (High pressure)
08: On/Off
0: Off (Close), 1: On (Open)
01
086
Pressure switch (Low pressure)
08: On/Off
0: Off (Close), 1: On (Open)
01
088
Crankcase heater output On/Off
08: On/Off
0: Off, 1: On
01
089
Base heater output On/Off
08: On/Off
0: Off, 1: On
01
090
Belt heater output On/Off
08: On/Off
0: Off, 1: On
01
100
Operating current
09: A
01
110
Outdoor unit total power-on hours
11: h
01
111
Compressor total heating operation
hours
11: h
6-13. Unit status monitoring and the detected value indication
- (04-26) -
6. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General AOHG45KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Page 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Page 36: ......
Page 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Page 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...