2-20. E: 94. Trip detection (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 94
Detective actuator
Outdoor unit
Inverter PCB
Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE:
The number of generations is reset when the
compressor starts up.
Main PCB
Compressor
Forecast of cause
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
Inverter PCB
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
•
No obstructions in air passages?
•
Heat exchange fins clogged
•
Outdoor unit fan motor check
•
Ambient temperature not raised by the effect of other heat sources?
•
Discharged air not sucked in?
↓
Check point 2. Replace inverter PCB
If Check point 1 do not improve the symptom, change inverter PCB.
↓
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom, change main PCB.
↓
Check point 4. Replace compressor
If Check point 3 do not improve the symptom, change compressor.
↓
End
2-20. E: 94. Trip detection (Outdoor unit)
- (03-26) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General AOHG45KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Page 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Page 36: ......
Page 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Page 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...