3-5. Details of control output function
¢
Operation status
Function
setting
External input and
output PCB
External output
Output signal
Status
Rotary switch
60-00
—
Output of indoor unit
CN47
Off → On
Operation
On → Off
Stop
—
1, B, C, D
External input and
output PCB
Ex OUT 1
Off → On
Operation
On → Off
Stop
The output is low when the unit is stopped.
CN47
On
Off
Ex OUT 1
Indoor unit operation
On
Off
On
Off
¢
Error status
Function
setting
External input and
output PCB
External output
Output signal
Status
Rotary switch
60-09
—
Output of indoor unit
CN47
Off → On
Error
On → Off
Normal
—
2
External input and
output PCB
Ex OUT 1
Off → On
Error
On → Off
Normal
—
1, C
External input and
output PCB
Ex OUT 2
Off → On
Error
On → Off
Normal
—
D
External input and
output PCB
Ex OUT 3
Off → On
Error
On → Off
Normal
The output is on when an error is generated for the indoor unit.
Error
Normal
On
Off
CN47
On
Off
Ex OUT 1, 2, 3
Indoor unit
3-5. Details of control output function
- (05-20) -
3. External input and output (For indoor unit)
FIELD
WORKING
FIELD
WORKING
Summary of Contents for General AOHG45KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Page 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Page 36: ......
Page 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Page 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...