1-4. Rotation number of compressor at normal start-up
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Frequency VI
Frequency VII
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Time 7
Frequency VIII
Time 8
Frequency IX
Frequency X
Time 9
Time 10
• Normal operation
Frequency
(rps)
I
II
III
IV
V
VI
VII
VIII
IX
X
41
46
51
57
60
72
81
91
100
110
Time (sec)
1
2
3
4
5
6
7
8
9
10
60
120
180
240
360
420
480
540
600
660
• Special operation
Frequency
(rps)
I
II
III
IV
V
VI
VII
VIII
IX
X
41
46
51
57
60
72
81
91
100
110
Time (sec)
1
2
3
4
5
6
7
8
9
10
120
185
245
305
605
665
725
785
845
1,000
NOTES:
• Normal operation:
– Cooling and dry mode
• Below 3 hours from the compressor stop and the compressor thermistor ≥ 15 °C
• After defrost operation
– Other than when the compressor starts for the first time since the breaker turns on
• Special operation:
– Other than the normal operation condition
– When the compressor starts for the first time since the breaker turns on
1-4. Rotation number of compressor at normal start-up
- (04-3) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for General AOHG45KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Page 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Page 36: ......
Page 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Page 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...