background image

En-2

When Connecting Refrigerant Tubing

• Keep all tubing runs as short as possible.
• Use the brazing method for connecting tubing.
• Apply refrigeration compressor oil (or equivalent) used for the outdoor unit to the match-

ing surfaces of the flare and union tubes before connecting them, then tighten the nut 
with a torque wrench for a leak free connection.

• Check carefully for leaks before starting the test run.

When Servicing...

• Turn the power OFF at the main circuit breaker panel before opening the unit to check or 

repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of 

wiring have been left inside the unit being serviced.

• After installing the unit, perform a test run to make sure the unit operates normally. Then, 

explain to the customer how to operate and maintain the unit.

• Please pass this Installation manual together with the Operating manual to the customer.

Please ask the customer to keep the Operating manual and Installation manual at hand 
for future reference during the moving or repair of the main unit.

WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or other 
prescribed parts.
Using non-specified parts will cause serious accidents such as falling unit, refrigerant 
leakage, water leakage, electric shock, and fire.

To install a unit that uses the R410A refrigerant, use dedicated tools and piping materi-
als that have been manufactured specifically for R410A use.
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than 
the R22, failure to use dedicated piping material or improper installation can cause 
rupture or injury.
It will also cause serious accidents such as refrigerant leakage, water leakage, electric 
shock, and fire.

Do not introduce any substance other than the prescribed refrigerant into the refrigera-
tion cycle.
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become 
abnormally high and cause the piping to rupture.

Ensure that the outdoor unit is securely installed at a place that can withstand the 
weight of the unit.
Improper installation will cause injuries caused by falling unit.

If there is a refrigerant leakage, make sure that it does not exceed the concentration 
limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as 
oxygen starvation.

If a refrigerant leakage occurs during operation, immediately vacate the premises and 
thoroughly ventilate the area.
If the refrigerant is exposed to fire, it will create a hazardous gas.

Electrical work must be performed in accordance with this Installation manual by a 
person certified under the national or regional regulations. Be sure to use a dedicated 
circuit for the unit.

For wiring, use the prescribed type of cables, connect them securely, making sure that 
there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as overheat-
ing the terminals, electric shock, or fire.

Do not turn ON the power until all work has been completed.

After the installation, make sure there is no refrigerant leakage.
If the refrigerant leaks into the room and becomes exposed to a source of fire such as a 
fan heater, stove, or burner, it will create a hazardous gas.

Use a wall hole pipe. Otherwise, it may cause a short circuit.

Do not place the outdoor unit near the handrail of the balcony.
Children may climb onto the outdoor unit, lean over the handrail and fall over.

Use only a specified power cable. Poor connection, poor insulation, and exceeding the 
allowable current will lead to electric shock and fire.

Install a breaker to cut off all AC main current at the same time.
If you do not install a breaker, it may cause electric shock and fire.

Be sure to install the refrigerant pipe before operating the compressor. If the refrigerant 
pipe is not installed and you operate the compressor while the valve is open, air will be 
sucked into the system and abnormal pressure will occur in the refrigerant cycle. This 
will damage the unit and cause injuries.

During the pump-down operation, make sure that the compressor is turned off be-
fore you remove the refrigerant piping. Do not remove the connection pipe while the 
compressor is in operation with 2-way or 3-way valve open. This may cause abnormal 
pressure in the refrigeration cycle that leads to breakage and even injury.

If there is a possibility of touching the fan during maintenance, make sure to turn OFF 
the power before implementing the maintenance. Even if operations are suspended, 
the fan of outdoor unit sometimes rotates, so if the fan rotates suddenly while in contact 
with you may cause serious injury.

Installation must be performed in accordance with the requirement of NEC (National 
Electrical Code) and CEC (Canadian Electrical Code) by authorized personnel only.

CAUTION

This unit must be installed by qualified personnel with a capacity certificate for handling 
refrigerant fluids. Refer to regulation and laws in use on installation place.

The installation must be carried out in compliance with regulations in force in the place 
of installation and the installation instructions of the manufacturer.

This unit is part of a set constituting an air conditioner. It must not be installed alone or 
with non-authorized by the manufacturer.

This unit contains no user-serviceable parts. Always consult authorized service person-
nel to repairs.

When moving, consult authorized service personnel for disconnection and installation 
of the unit.

• Obtain the distribution network operator's agreement about the power capacity of the 

power supply system, specification of the cable and the harmonic current, and etc. 
when you connect the outdoor unit with the power supply.

• This unit must be connected to a power supply with impedance of 0.398 ohm and 

below. If the power supply does not satisfy this requirement, please consult the power 
supplier.

• This product is intended for professional use.

Be sure to use a dedicated power circuit.
Never use a power supply shared by another appliance.

Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

• Area filled with mineral oil or containing a large amount of splashed oil or steam, such 

as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak 
water. 

• Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to 
corrode, which can cause refrigerant leakage.

• Area containing equipment that generates electromagnetic interference. It will cause 

the control system to malfunction, preventing the unit from operating normally.

• Area that can cause combustible gas to leak, contains suspended carbon fibers or 

flammable dust, or volatile inflammables such as paint thinner or gasoline. If gas leaks 
and settles around the unit, it can cause a fire.

• Avoid installing the unit at places where it will come into contact with animals’ urine or 

ammonia.

The units are not explosion proof and therefore should not be installed in explosive 
atmosphere.

Do not use the unit for special purposes, such as storing food, raising animals, growing 
plants, or preserving precision devices or art objects. It can degrade the quality of the 
preserved or stored objects.

Perform draining for the unit according to the Installation manual. Check that the water 
is properly drained. If the drain processing is improperly installed, water may drip down 
from the unit, wetting the furniture.

Be sure not to start or stop the operation of air conditioning with power breaker. Other-
wise, it may cause malfunction or water leakage.

When setting it up near the equipment that generates electromagnetic waves and the 
equipment that generates the higher harmonics wave, be sure to take measures against 
noise. Otherwise, it may cause malfunction or failure.

When energizing to the crankcase heater, please turn on the power 12 hours or earlier 
before operation begins. When the energizing time is short, it may cause failure. Be-
sides, please do not turn off power during the busy season.

Children should be monitored to ensure they do not play with the device.

This product is not intended to be used by people (including children) with physical, 
sensory or mental disability, or persons lacking experience or knowledge unless they 
have been given by the through a person responsible for their safety, supervision or 
instruction concerning the use of the device.

2.  ABOUT THIS PRODUCT

2.1.  Precautions for using R410A refrigerant

Pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of R22 models, some of the 
piping and installation and service tools are special. (See the table in the SPECIAL 
TOOLS FOR R410A section.)
Especially, when replacing a conventional refrigerant (other than R410A) model with 
a new refrigerant R410A model, always replace the conventional piping and flare nuts 
with the R410A piping and flare nuts.

Models that use refrigerant R410A have a different charging port thread diameter to pre-
vent erroneous charging with R22, R407C and for safety. Therefore, check beforehand. 
[The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]

Be more careful than the installation of the refrigerant (other than R410A) models, not 
to enter foreign matters (oil, water, etc.) and other refrigerant into the piping. Also, when 
storing the piping, securely seal the openings by pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition 
of the gas and liquid phases, and always charge from the liquid phase side whose 
composition is stable.

9380545187-02_IM.indb   2

9380545187-02_IM.indb   2

12/15/2016   2:17:06 PM

12/15/2016   2:17:06 PM

Summary of Contents for Airstage AOU36RLAVS

Page 1: ...ACIÓN OUTDOOR UNIT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado AOU36RLAVS AOU48RLAVS 9380545187 02_IM indb cover1 9380545187 02_IM indb cover1 12 15 2016 2 17 06 PM 12 15 2016 2 17 06 PM ...

Page 2: ...lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can caus...

Page 3: ...e and CEC Canadian Electrical Code by authorized personnel only CAUTION This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instructions of the manufacturer...

Page 4: ...talled 1 000 ft m If the results of the calculation exceed the concentration limit increase the room surface area or install a ventilation duct CAUTION Please install the outdoor unit without slant within 3 degrees Install this unit in a location with good ventilation If the unit must be installed in an area within easy reach of the general public install as necessary a protective fence or the lik...

Page 5: ...0 3 3 2 Multiple outdoor unit installation Provide at least 1 in 25 mm of space between the outdoor units if multiple units are installed When routing the piping from the side of an outdoor unit provide space for the piping No more than 3 units must be installed side by side When 3 units or more are arranged in a line provide the space as shown in the following example when an obstruction is prese...

Page 6: ... is brazed without applying nitrogen gas it will create an oxidation film This can degrade performance or damage the parts in the unit such as the compressor or valves Do not use flux to braze pipes If the flux is the chlorine type it will cause the pipes to corrode In addition if the flux contains fluoride it will affect the refrigerant piping system due to deterioration of refrigerant oil For br...

Page 7: ...onnection Lateral connection Bottom connection Rear connection 5 4 Pipe connection CAUTION Do not use mineral oil on a flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units While brazing the pipes be sure to blow dry nitrogen gas through them The maximum lengths of this product are shown in the table If the units are further apart than this cor...

Page 8: ...arate these cable by 2 in 50 mm or more Bundling these cables together will cause miss operation or breakdown Always keep to the maximum length of the transmission cable Exceeding the maximum length may lead to erroneous operation The static electricity that is charged to the human body can damage the control PC board when handling the control PC board for address setting etc Please keep caution t...

Page 9: ... power supply cable Indoor unit power supply cable Breaker 2 Breaker 1 Breaker 2 6 4 Transmission line CAUTION Caution when wiring cable When stripping off the coating of lead wire always use the exclusive tool such as a wire stripper If there is no exclusive tool available necessarily carefully strip the coat ing by a cutter etc so that the conductive wire is not damaged If it is damaged it may l...

Page 10: ...hown in figure 6 5 2 Wiring procedure Remove the service panel And connect the cable to the terminal in accordance with the terminal name plate Use a ring terminal to connect the electric cables to the power supply terminal board Keep the earth cable longer than the other cables After connecting the electric cable secure them with a cable clamp Connect the cable without applying excessive tension ...

Page 11: ...put cable with appropriate external dimension depending on the number of cables to be installed For each input pin No 1 is of positive polarity and pin No 2 is of ground level connected unit connected unit connected unit connected unit connected unit Input 1 CN131 Yellow Input 2 CN132 Green Input 3 CN133 White Input 4 CN134 Red Input 5 CN135 Orange P C B Operation behavior Each input terminal work...

Page 12: ...etting CAUTION Be sure to set the terminal resistor according to specifications Set the terminal resistor for every network segment NS If terminal resistor is set in multiple devices the overall communication system may be damaged If terminal resistor is not set in a device abnormal communication may occur Be sure to set 1 terminal resistor in a network segment You can set the terminal resistor at...

Page 13: ...orbidden 3 4 0 0 Factory default 35 Presence of heater selection control using outdoor tempera ture 1 Invalid 3 5 0 0 Valid 0 1 If Heater selection control 1 or 2 using outdoor temperature is used for any of the indoor units of the refrigerant system select Valid For more details on settings for this item see the Design Technical Manual 36 Outdoor tempera ture zone bound ary temperature A 1 4 0 F ...

Page 14: ...gnal amplifiers When using signal amplifiers the address for signal amplifiers must be set The address for signal amplifiers can be set automatically from 1 outdoor unit master unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address sett...

Page 15: ... cap Hexagon wrench 4 mm 5 32 Table A Pipe 3 way valve Blank cap Charging port cap Liquid valve 5 2 to 6 6 lbf ft 7 0 to 9 0 N m 14 8 to 18 5 lbf ft 20 0 to 25 0 N m 9 2 to 11 8 lbf ft 12 5 to 16 0 N m Gas valve 8 1 to 9 6 lbf ft 11 0 to 13 0 N m 22 1 to 25 8 lbf ft 30 0 to 35 0 N m 9 2 to 11 8 lbf ft 12 5 to 16 0 N m 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen ...

Page 16: ... wrench 8 3 2 Checking total amount of refrigerant and calculating the amount of refrigerant charge to be added The amount of refrigerant charge to be added is the total value of the basic refrigerant charge amount and the value calculated from the length of the liquid pipe Round up the value to 2 decimal places Model B Factory charged amount lb kg Diameter of liquid pipe in mm a Additional amount...

Page 17: ... capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the over lap indoor unit exist press SELECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation ch...

Page 18: ...it compressor 1 temperature error E A 4 1 Outdoor unit high pressure error E A 5 1 Outdoor unit low pressure error E A C 4 Outdoor unit heat sink temperature error t L 7 H J 6 A C E F d n o r 9 P U S 8 5 3 4 1 2 0 7 segment LED indicator Test operation setting method Use the MODE EXIT SELECT and ENTER buttons on the indoor unit PC board to configure settings according to the procedures below Setti...

Reviews: