background image

En-17

10. LED STATUS

You can determine the operating status by the lighting up and blinking of the LED display.
Check the status using the table below.

10.1. Normal operation codes

Mode

Code

Description

Operation

C

L

Cooling

H

t

Heating

o

r During oil recovery operation

d

F During defrosting operation

P C During power saving operation

L

n During low noise operation

10.2. Error codes

Mode

Code

Description

Communication 
error

E

1 4. 2 Outdoor unit network communication 2 error

E

1 4. 5 The number of indoor unit shortage

Function setting 
error

E

2 2. 1 Indoor unit capacity error

E

2 4. 2 Connection unit number error (Indoor unit)

E

2 6. 1 Indoor unit duplicate address error

E

2 8. 1 Auto address setting error

E

2 8. 4 Signal amplifier auto address error

Indoor unit 
actuator error

E

5 U. 1 Indoor unit miscellaneous error

Outdoor unit 
PCB/Electrical 
component/ 
Switch error

E

6 2. 3 Outdoor unit EEPROM access error

E

6 2. 6 Outdoor unit inverters communication error

E

6 2. 8 Outdoor unit EEPROM data corruption error

E

6 3. 1 Outdoor unit inverter error

E

6 7. 2

Outdoor unit inverter PCB power short interruption 
error

E

6 8. 2

Outdoor unit rush current limiting resister temp. rise error 
(protective operation)

E

6 9. 1

Outdoor unit transmission PCB parallel communica-
tion error

Outdoor unit 
sensor error

E

7 1. 1 Outdoor unit discharge temp. thermistor 1 error

E

7 2. 1 Outdoor unit compressor temp. thermistor 1 error

E

7 3. 3 Outdoor unit heat ex. liquid temp. thermistor error

E

7 4. 1 Outside air temp. thermistor error

E

7 5. 1 Outdoor unit suction gas temp. thermistor error

E

7 7. 1 Outdoor unit heat sink temp. thermistor error

E

8 4. 1

Outdoor unit current sensor 1 error 
(permanent stop)

E

8 6. 1 Outdoor unit discharge pressure sensor error

E

8 6. 3 Outdoor unit suction pressure sensor error

Outdoor unit 
actuator error

E

9 3. 1 Outdoor unit inverter compressor start up error

E

9 4. 1 Outdoor unit trip detection

E

9 5. 5 Outdoor unit compressor motor loss of synchronization

E

9 7. 1 Outdoor unit fan motor 1 lock error

E

9 7. 4 Outdoor unit fan motor 1 undervoltage error

E

9 7. 5

Outdoor unit fan motor 1 temperature error 
(protective action)

E

9 A. 1 Outdoor unit coil 1 (expansion valve 1) error

Refrigerant 
system error

E A 1. 1

Outdoor unit discharge temperature 1 error (permanent 
stop)

E A 3. 1 Outdoor unit compressor 1 temperature error
E A 4. 1 Outdoor unit high pressure error
E A 5. 1 Outdoor unit low pressure error
E A C. 4 Outdoor unit heat sink temperature error

,,

,

,

,

,

,

,

,

,

,

t:

L:

7:

H:

J:

6:

A:

C:

E:

F:

,

,

,

d:

n:

o:

r:

,

,

,

,

,

9:

P:

U:

S:

8:

,

,

,

,

5:

3:

4:

1:

2:

,

0:

7 segment LED indicator:

Test operation setting method

Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the indoor unit PC board to 
configure settings according to the procedures below.

Settings for starting test run 
operation

Settings for stopping test run 
operation

Press the “ENTER” button for 
more than 3 seconds.

Press the “ENTER” button for more than 3 seconds.

Press the “ENTER” button for 
more than 3 seconds.

This will be displayed when the cooling operation mode is 
canceled.

This will be displayed 
when the cooling test 
operation is complete.

This will be displayed 
when the heating test 
operation is complete.

This will be displayed after 5 seconds.

This will be displayed after 5 seconds.

First 2 digits Last 2 digits

Set to Function mode [F3].
(When [F4] to [F9] are displayed, continue to 
press the “SELECT” button until [F3] is displayed.)

For heating operation, press the “SELECT” 
button until “01” is displayed.

Function settings

EXIT

After the test operation is complete, turn off the power. Attach the cover of the electrical 
component box and the front panel of the outdoor unit.

NOTES:

• Check that the indoor and outdoor units connected to the same refrigerant system are 

operating normally.

• When indoor or outdoor units are not operating, or when the indoor and outdoor units 

of other refrigerant systems are operating, the indoor/outdoor unit address are not 
configured correctly.

• The system will not operate normally with an incorrect DIP switch setting.

Stop the system immediately and recheck the DIP switch setting.

9.4. Checklist

Check description

Check method

Criteria

1

High and low pressure values 
are normal.

Check it with a pres-
sure gauge.

Cooling: low pressure ap-
prox. 116 psi (0.8 MPa)
Heating: high pressure ap-
prox. 435 psi (3.0 MPa)

2

Drain water is discharged 
smoothly through the drain 
hose.

Check it by pouring 
water.

3

Indoor and outdoor unit fans 
are operating.

Check them visually.

4

Compressor operates after 
the indoor unit operates.

Check the operating 
sound.

5

Difference between inlet and 
outlet temperatures is normal.

Measure the inlet and 
outlet temperatures.

Temperature difference 10 
degrees

6 Error is not displayed

Check the 7 segment 
LED display

Error blinking or no error 
code display

9380545187-02_IM.indb   17

9380545187-02_IM.indb   17

12/15/2016   2:17:09 PM

12/15/2016   2:17:09 PM

Summary of Contents for Airstage AOU36RLAVS

Page 1: ...ACIÓN OUTDOOR UNIT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado AOU36RLAVS AOU48RLAVS 9380545187 02_IM indb cover1 9380545187 02_IM indb cover1 12 15 2016 2 17 06 PM 12 15 2016 2 17 06 PM ...

Page 2: ...lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can caus...

Page 3: ...e and CEC Canadian Electrical Code by authorized personnel only CAUTION This unit must be installed by qualified personnel with a capacity certificate for handling refrigerant fluids Refer to regulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instructions of the manufacturer...

Page 4: ...talled 1 000 ft m If the results of the calculation exceed the concentration limit increase the room surface area or install a ventilation duct CAUTION Please install the outdoor unit without slant within 3 degrees Install this unit in a location with good ventilation If the unit must be installed in an area within easy reach of the general public install as necessary a protective fence or the lik...

Page 5: ...0 3 3 2 Multiple outdoor unit installation Provide at least 1 in 25 mm of space between the outdoor units if multiple units are installed When routing the piping from the side of an outdoor unit provide space for the piping No more than 3 units must be installed side by side When 3 units or more are arranged in a line provide the space as shown in the following example when an obstruction is prese...

Page 6: ... is brazed without applying nitrogen gas it will create an oxidation film This can degrade performance or damage the parts in the unit such as the compressor or valves Do not use flux to braze pipes If the flux is the chlorine type it will cause the pipes to corrode In addition if the flux contains fluoride it will affect the refrigerant piping system due to deterioration of refrigerant oil For br...

Page 7: ...onnection Lateral connection Bottom connection Rear connection 5 4 Pipe connection CAUTION Do not use mineral oil on a flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units While brazing the pipes be sure to blow dry nitrogen gas through them The maximum lengths of this product are shown in the table If the units are further apart than this cor...

Page 8: ...arate these cable by 2 in 50 mm or more Bundling these cables together will cause miss operation or breakdown Always keep to the maximum length of the transmission cable Exceeding the maximum length may lead to erroneous operation The static electricity that is charged to the human body can damage the control PC board when handling the control PC board for address setting etc Please keep caution t...

Page 9: ... power supply cable Indoor unit power supply cable Breaker 2 Breaker 1 Breaker 2 6 4 Transmission line CAUTION Caution when wiring cable When stripping off the coating of lead wire always use the exclusive tool such as a wire stripper If there is no exclusive tool available necessarily carefully strip the coat ing by a cutter etc so that the conductive wire is not damaged If it is damaged it may l...

Page 10: ...hown in figure 6 5 2 Wiring procedure Remove the service panel And connect the cable to the terminal in accordance with the terminal name plate Use a ring terminal to connect the electric cables to the power supply terminal board Keep the earth cable longer than the other cables After connecting the electric cable secure them with a cable clamp Connect the cable without applying excessive tension ...

Page 11: ...put cable with appropriate external dimension depending on the number of cables to be installed For each input pin No 1 is of positive polarity and pin No 2 is of ground level connected unit connected unit connected unit connected unit connected unit Input 1 CN131 Yellow Input 2 CN132 Green Input 3 CN133 White Input 4 CN134 Red Input 5 CN135 Orange P C B Operation behavior Each input terminal work...

Page 12: ...etting CAUTION Be sure to set the terminal resistor according to specifications Set the terminal resistor for every network segment NS If terminal resistor is set in multiple devices the overall communication system may be damaged If terminal resistor is not set in a device abnormal communication may occur Be sure to set 1 terminal resistor in a network segment You can set the terminal resistor at...

Page 13: ...orbidden 3 4 0 0 Factory default 35 Presence of heater selection control using outdoor tempera ture 1 Invalid 3 5 0 0 Valid 0 1 If Heater selection control 1 or 2 using outdoor temperature is used for any of the indoor units of the refrigerant system select Valid For more details on settings for this item see the Design Technical Manual 36 Outdoor tempera ture zone bound ary temperature A 1 4 0 F ...

Page 14: ...gnal amplifiers When using signal amplifiers the address for signal amplifiers must be set The address for signal amplifiers can be set automatically from 1 outdoor unit master unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address sett...

Page 15: ... cap Hexagon wrench 4 mm 5 32 Table A Pipe 3 way valve Blank cap Charging port cap Liquid valve 5 2 to 6 6 lbf ft 7 0 to 9 0 N m 14 8 to 18 5 lbf ft 20 0 to 25 0 N m 9 2 to 11 8 lbf ft 12 5 to 16 0 N m Gas valve 8 1 to 9 6 lbf ft 11 0 to 13 0 N m 22 1 to 25 8 lbf ft 30 0 to 35 0 N m 9 2 to 11 8 lbf ft 12 5 to 16 0 N m 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen ...

Page 16: ... wrench 8 3 2 Checking total amount of refrigerant and calculating the amount of refrigerant charge to be added The amount of refrigerant charge to be added is the total value of the basic refrigerant charge amount and the value calculated from the length of the liquid pipe Round up the value to 2 decimal places Model B Factory charged amount lb kg Diameter of liquid pipe in mm a Additional amount...

Page 17: ... capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the over lap indoor unit exist press SELECT button to switch to the next error If error occurs it will display Ad address number 9 2 Test run Before the test operation ch...

Page 18: ...it compressor 1 temperature error E A 4 1 Outdoor unit high pressure error E A 5 1 Outdoor unit low pressure error E A C 4 Outdoor unit heat sink temperature error t L 7 H J 6 A C E F d n o r 9 P U S 8 5 3 4 1 2 0 7 segment LED indicator Test operation setting method Use the MODE EXIT SELECT and ENTER buttons on the indoor unit PC board to configure settings according to the procedures below Setti...

Reviews: